Serial Status DCA  
Configuration Guide  
 
 
A166-0CG-1.00-2 Restricted 
12 
 Full 
 
Remedy: 
• 
Ensure the CFG_DCA table in the WIN application is configured with a record containing 
the WESDAC points to be allocated for the Serial Status DCA
• 
Ensure the DCA Index configured in A166APPL points to the correct record in the WIN 
CFG_DCA table. 
A.2 Non-Fatal 
Error 
Messages 
These messages indicate the application has encountered a non-fatal configuration error or a non-
fatal stage of process initialization failed. The application will not suspend as a whole, but rather 
attempt to run in a limited or reduced capacity. 
E001: Child Died !!! 
Cause 
• 
One of the Serial Status DCA processes stopped unexpectedly. If this error occurs, the 
system has become unstable. 
Effect: 
• 
Serial Status DCA functionality will become unreliable. 
Remedy: 
• 
Contact the Customer Service Department and report this error. 
 
E002: Error creating message exchange, sts=<x> 
Cause 
• 
The system was unable to create one of the required message exchanges. 
Effect: 
• 
One scan and one communication process will not be started. As a result, the Serial Status 
DCA will be unable to communicate over one of the configured communication ports. 
Remedy: 
• 
Note the return status, <x>, and contact the Customer Service Department to report this error. 
 
E003: Unable to spawn com process, rec <x> 
Cause 
• 
The system encountered an error while trying to spawn one of the communication processes. 
Effect: 
• 
One of the communication processes will not be started. As a result, the Serial Status DCA 
will be unable to communicate over the communication port configured in record <x> of 
A166PORT. 
Remedy: 
• 
Contact the Customer Service Department and report this error.