Mitsubishi Electronics AJ65BT-D75P2-S3 Benutzerhandbuch

Seite von 666
 
 
 
4 - 27 
MELSEC-A
4      INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT 
 
(Step 3)   Operation monitor 2 
 
1)  The axis display LED for each axis will turn ON sequentially at an approx. 
0.5 second interval. 
 
One of the following states will appear on the 17-segment LED to indicate 
the state of the axis for which the axis display LED is ON. 
 
Confirm that the display matches each axis state. 
 
Axis state 
17-segment 
LED 
Remarks 
Idle IDLE 
 State when power is turned 
ON/operation has ended. 
Stopped STOP 
 State when positioning 
operation is temporarily 
stopped. 
In JOG operation 
JOG 
– 
In manual pulse generator operation 
MANP 
In zero point return 
OPR 
In position control 
POSI 
In speed control 
VELO 
In speed control for speed/position changeover control 
V- P 
In position control for speed/position changeover control
V -P 
Waiting BUSY 
 The execution is waiting due to 
the condition designation, etc. 
Error occurrence * 
E*** 
 The error code appears in ***. 
Refer to Chapter 14 for details 
on the errors. 
 
POINT 
 
      *    When the Remote station READY signal (RX(n+7)B) is ON, even if a 
parameter error occurs, the error code will not appear on the 17-segment LED. 
If the error code is not displayed on the 17-segment LED, check the error code 
with the peripheral device or D75P2 "Axis error No. (RWrn+5, RWrn+13)", 
"Axis warning No. (RWrn+6, RWrn+14)". 
 
2)  When the mode switch is pressed, the state will shift to the internal 
information 1 monitor state described in (Step 4). 
 
(Step 4)      Internal information 1 monitor 
 
1)  The D75P2 OS type ("S003") will appear on the 17-segment LED for 
reference. 
2)  The axis display LED for each axis will turn OFF. 
3)  When the mode switch is pressed, the state will shift to the internal 
information 2 monitor state described in (Step 5).