Appendix - 20 
MELSEC-A
APPENDICES 
 
Appendix 5.3 Connection example of D75P2 and MR-C A  
 
 
(Differential driver (Open collector)) *
5
 
 
 
*1  Assignment of the pin numbers of the connector of the D75P2 is the same for axis 1 and axis 2. 
*2  The upper limit (FLS) and lower limit (RLS) of the D75P2 are used for the zero point return retry function. 
 
Set these inside the limit switches for the servo. 
*3  Limit switch for servo (stopping). 
*4  The distance between the controller and amplifier is indicated. 
 
The distance must be within 2m with the open collector. 
*5  Use “Logic selection for pulse output to the drive unit” specified in detailed parameter 1 to match the logic (positive 
or negative logic) between the D75P2 and the servo amplifier. The initial setting of D75P2 is a positive logic. 
*6  There is no need to wire the in-position signal (It is output as in-position signal (RX(n+1)4, RX(n+4)4) but it is not 
used for internal processes of the D75P2.) 
 
REMARK 
The AD75C20SC cable (for differential driver) can be used for the connection between the D75P2 and MR-C A. 
(Refer to section "2.2 List of configuration devices.")