Impinger I -–1000 Series Service Manual - Domestic 
27 
Speed Control Potentiometer  This is a 0 to 400 ohm or 0 to 500 ohm, 10-turn 
potentiometer. WITH POWER OFF: remove the 
red, white, and black leads from terminals S1, S2, 
S3. With a digital multimeter, check the ohm 
reading across the red to black leads. This ohm 
reading should be a steady 400-ohm, or 500-ohm, 
through the entire 10-turn rotation of the 
potentiometer. Check for shorts or opens or 
unsteady, ohm reading, if potentiometer is 
defective, replace. If the potentiometer checks OK, 
and there is no output at terminals A1 and A2, 
replace the D. C. control board. 
Reversing Switch 
If there is D. C. voltage output from the motor 
control board, but the conveyor drive motor is not 
running, check the D.P.D.T. reversing switch. 
 
Conveyor Drive Motor 
Check the conveyor drive sprocket for tightness. 
Disconnect the motor, check the red and black 
motor leads for opens, shorts or grounds. Check 
the brushes for excessive or 
 abnormal wear. 
Replace as needed. Reconnect motor. Test for 
operation. If motor does not run, replace. 
Voltage Supply 
Check incoming voltage supply at line 1 to neutral. 
There should be a voltage reading of 120 VAC. If 
no present, check breakers. 3 Amp Fuse. This 
conveyor fuse is located on the front panel. 
Replace if defective. 
Fuseholder 
Check and/or Replace. 
Fan Switch 
See procedure for checking on Page 20. 
Conveyor will not 
run(S/N 4390 to 
Q190771000 Series) 
(S/N 4390-
Q147901200 Series) 
Conveyor Switch 
Same procedure as for fan switch. 
(Dual Belt Ovens) 
Dual belt ovens utilize 2 complete independent 
conveyor drive systems. The trouble shooting 
procedures are the same as single belt ovens, 
except that the dual belt ovens use one each of the 
following: one "A" D. C. control board and one "B" 
D. C. control board. 
NOTE: 
Speed Adjustment 
Potentiometer 
This is a 0 to 5 K ohm, 10 turn potentiometer With 
power off, remove the red, black and white pot 
leads from the motor control board at terminals P1, 
P2 and P3. With a digital multimeter, check the 
ohm reading across the red lead (P3) to the black 
lead (P1). This reading should be 5 K ohms ± 5% 
as the pot is rotated from low to high. Place the 
meter leads on the red lead (P3) and on the white 
lead (P2) Rotating the pot. slowly, from low to high, 
the meter reading should show an even transition 
from O to 5 K ohms ± 5%. There should be 
 
DC Motor Control Board 
Check for 120 VAC input to the control board at 
terminals L1 and L2. If not present, check the 
conveyor switch and wiring back to 3-amp fuse and 
then back to power source if necessary. If 120 VAC 
is present at L1 and L2, check the VDC output at 
terminals A+ and A-. If a DC voltage is not present, 
check the 4 amp and the 1 amp fuses on the 
control board. Also reset and check the mini 
breaker in the armature line to the gearmotor. If 
120 VAC is present at terminals L1 and L2, but DC 
voltage is not present at A+ and A-, providing the 1 
amp and 4 amp fuses are good, replace the board. 
If DC voltage is present at A+ and A-, but motor 
does not run, check gear motor as follows.