The following applies when using tankless water heaters to recover a storage tank.            
Drawing WH-1-B is an example. 
Tankless water heaters have a pressure loss which must be 
             considered in the system design.  
Reference the pressure loss curve for the heater model being used to determine the pump size for the
  
desired recovery rate. 
For recommended pump sizes use the table below.  Additional pressure losses in plumbing between the 
Heater(s) and the storage tank must also be taken into consideration. 
The specified pump size is to provide maximum recovery of the storage tank.  A smaller pump size may 
be used, but could result in longer recovery time of the tank.  Please contact the Tech Services department 
with any questions on pump sizing.  
NOTE: 
Only use pumps of brass or stainless steel construction.  Do not use pumps of iron 
construction as they will oxidize and clog the inlet filter on the appliance. 
Pump Sizing for Storage Tank Application 
7
Pump Flow Requirements 
Number of 
Tankless
Water Heaters 
 
705/505 
305 
6 gpm @ 30' head 
5 gpm @ 25' head 
12 gpm @ 30' head 
10 gpm @ 25' head 
18 gpm @ 30' head 
15 gpm @ 25' head 
24 gpm @ 30' head 
20 gpm @ 25' head 
30 gpm @ 30' head 
25 gpm @ 25' head 
36 gpm @ 30' head 
30 gpm @ 25' head 
42 gpm @ 30' head 
35 gpm @ 25' head 
48 gpm @ 30' head 
40 gpm @ 25' head 
54 gpm @ 30' head 
45 gpm @ 25' head 
10 
60 gpm @ 30' head 
50 gpm @ 25' head 
11 
66 gpm @ 30' head 
55 gpm @ 25' head 
12 
72 gpm @ 30' head 
60 gpm @ 25' head 
13 
78 gpm @ 30' head 
65 gpm @ 25' head 
14 
84 gpm @ 30' head 
70 gpm @ 25' head 
15 
90 gpm @ 30' head 
75 gpm @ 25' head