BLS/E/20W/CMH
BLS/E/35W/CMH
BLS/E/20W/CMH/R
BLS/E/35W/CMH/R
BLS/E/70W/CMH
BLS/E/70W/CMH/R
BLS/E/150W/CMH
BLS/E/150W/CMH/R
Control gear and accessories
Electronic Ballasts
A range of GE electronic ballasts have been introduced to complement the 20, 35, 70 and 150W ConstantColor™
Ceramic Metal Halide lamps
Power controlled electronic ballasts suitable for operation of Ceramic Metal Halide lamps are available from various gear 
manufacturers.
Advantages are: 
• Good regulation against supply voltage variation
• Improved lamp colour consistency
• Elimination of lamp flicker
• Reduced weight of control gear
• Reduced electrical power losses
• Ballast noise reduced/eliminated 
• Single piece compact unit
• Reduced wiring complexity in the luminaire 
Features
• Integral version with open terminals for embodiment into luminaire
• Remote version with terminal cover and cable strain relief for location outside the luminaire
• 50,000 hours service life under the specified conditions
• Reduced power consumption compared to electromagnetic circuits
• Reduced component count and simplified wiring compared to electromagnetic circuits
• Rapid and controlled power run-up 
• Lamp life maximised by square-wave current and constant lamp power
• Excellent lamp colour stability throughout life 
• Automatic lamp failure shut-down 
• Timed restart after mains voltage interruption
• Immune to mains voltage variations
General Information
Watts
Volts
Description
Mounting
Weight
Pack Qty
Product Code
20
220-240
BLS/E/20W/CMHSMP
Integral
110 g
12
42387
20
220-240
BLS/E/20W/CMH
Integral
190 g
12
13032
20
220-240
BLS/E/20W/CMH/R
Remote
230 g
12
13034
35
220-240
BLS/E/35W/CMH
Integral
215 g
12
13035
35
220-240
BLS/E/35W/CMH/R
Remote
230 g
12
13036
70
220-240
BLS/E/70W/CMH
Integral
300 g
12
13040
70
220-240
BLS/E/70W/CMH/R
Remote
310 g
12
13047
150
220-240
BLS/E/150W/CMH
Integral
430 g
12
13050
150
220-240
BLS/E/150W/CMH/R
Remote
445 g
12
13053
System Performance
20W
35W
70W
150W
System Power
W
23.5
43
78
159
System
lm/W
72
79
79
88
Lumens*
lm
1700
3400
6200
14000
Lamp Power
W
20
39
72
146
Lamp Efficacy
lm/W
85
87
86
96
Lamp Voltage Range
V
70…125
70…125
70…125
70…125
* Data shown relates to 3000K products. Please see lamp data sheets for performance of equivalent 4200K rated products.
Operating Characteristics
20W
20W
35W
70W
150W
Mains Voltage
V
220...240
220...240
220...240
220...240
220...240
Mains Current
A
0.19
0.10
0.18
0.33
0.69
Mains Frequency
Hz
50
50...60
50...60
50...60
50...60
Power Factor
> 0.55
> 0.95
> 0.95
> 0.95
> 0.95
Allowed Mains Voltage Range
V
198...264
198...264
198...264
198...264
198...264
Ignition Voltage*
kV
< 3.5
< 2.5
< 2.5
< 2.5
< 2.5
Lamp Operating Frequency
Hz
133
150
150
150
150
Max Cable Capacitance
pF
1000
1000
3000
3000
3000
Max Lamp Distance**
m
2
10
25
25
25
Ambient Temperature Range
°C
-20...+50
-20...+50
-20...+50
-20...+50
-20...+50
Maximum Case Temperature
°C
80
75
75
75
80
Thermal Cut-off on PCB
°C
110
110
110
110
110
* If a hot lamp or no lamp is detected the ballast will attempt to start the lamp after one minute, if not successful further attempts are made up to a maximum 
of 4 times in 5 minute cycles, then if not successful the ballast will shut-down. The ballast is reset automatically by a supply interruption.
** Typical value if cable capacitance is below the specifi ed limit
Dimension
BLS/E/20W/
CMHSMP
BLS/E/20W/CMH
BLS/E/35W/CMH
BLS/E/70W/CMH
BLS/E/20W/CMH/R
BLS/E/35W/CMH/R
BLS/E/70W/CMH/R
BLS/E/150W/CMH
BLS/E/150W/CMH/R
Circuitry
Wire cross section: 0.75...2.5 mm
2
112,5
101,5
36
31
36
72
4,2
31
123
98
4,2
32,5
A
126
5,2
73
90
120
137
40
B
126
5,2
90
73
120
177
40
C
5,2
45,5
126
130
73
91
142,5
37
D
5,2
45,5
121
130
73
91
172
37
E
The ballasts comply with the relevant 
parts of the following standards:
– RFI suppression EN 55015
– Harmonics EN 61000-3-2
– Immunity EN 61547
– Safety EN 60926/EN 60928/EN 61347
– Performance EN 60927/EN 60929
A
 