The following formula can be used to determine the maximum heater rating per the definition of unconfined space:
BTU/Hr = (L
1
 + L
2
) Ft x (W) Ft x (H) Ft 
50
Consider two connecting rooms with an open area between, with the following dimensions: 
L
1
 = 15
1
/
2
 Ft., L
2
 = 12 Ft., W = 12 Ft., H = 8 Ft.
BTU/Hr = (15
1
/
 + 12) x (12) x (8)
50
If there were a door between the two rooms the calculation would be based only on the room with the heater.
BTU/Hr = (15
1
/
2
) x (12) x (8)
50
Figure 2 - Example of a Large Room with 1/2 Wall Divider 
Counter 
Cast Iron Stove 
x 1000
x 1000 = 52800 BTU/Hr
x 1000 = 29760 BTU/Hr
If  the  area  in  which  the  heater  may  be  operated  is  smaller  than  that  defined  as  an 
unconfined space or if the building is of unusually tight construction, provide adequate 
combustion and ventilation air by one of the methods described in the National Fuel 
Gas Code, ANSI Z223.1, NFPA54, Section 5.3 or applicable local codes.
W
ARNING
GENERAL INSTALLATION INFORMATION