Toshiba RAV-SM566KRT-TR Benutzerhandbuch

Seite von 112
10-4. Function Selection Setup (Wired Remote Controller Only)
<Procedure> Perform setting while the air conditioner stops.
1
Push 
TEST
 + 
SET
 + 
CL
 buttons simultaneously for 4 seconds or more.
The first displayed unit No. is the header indoor unit address in the group control.
In this time, fan and louver of the selected indoor unit operate.
ò
2
Every pushing 
UNIT  LOUVER
 button (button at left side), the indoor unit No. in the group control is
displayed one after the other. In this time, fan and louver of the selected indoor unit only operate.
ò
3
Using the set temperature 
TEMP.
 buttons, specify the CODE No. (DN).
ò
4
Using the timer time 
TIME
 buttons, select the SET DATA.
ò
5
Push 
SET
 button. (OK if indication lights)
• To change the selected indoor unit, proceed to Procedure 
2
 .
• To change CODE No. to be set up, proceed to Procedure 
3
 .
ò
6
Pushing 
TEST
 button returns the status to the normal stop status.
1    2    3    4    5    6
  END   
<Operation procedure>
3
6
1
4   
5   
2   
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT  LOUVER
FILE NO. SVM-12004
– 
68
 –