SS-CPC36-72
  
www.goodmanmfg.com 
7
h
eat
 k
it
 e
leCtriCal
 d
ata
 (B
lower
 o
nly
, h
eat
 m
ode
) — 3 t
ons
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
Multiply rated kW by correction factor to get actual kW
kW Correction Factor for 480V Units
Actual Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage use voltage
2
 / 480
2
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW
k
w C
orreCtion
 f
aCtor
Model and 
Heat Kit Usage
MCA¹ at 
208 / 240V
MOP² (amps) 
at 208 / 240V
Actual kW & 
BTU at 240V
Recommended
Airflow Range
CPC036***1D***
25
40
EHK1-10
48 / 55
50 / 60
10
1250-1350 CFM
EHK1-15
70 / 81
80 / 90
15
1400-1440 CFM
CPC036***3D***
17
25
EHK3-10
29 / 33
30 / 35
10
1250-1350 CFM
EHK3-15
42 / 48
45 / 50
15
1400-1440 CFM
CPC036***3B***
18
25
EHK3-10
30 / 33
35 / 35
10
1250-1350 CFM
EHK3-15
43 / 48
45 / 50
15
1400-1440 CFM
Model and 
Heat Kit Usage
MCA¹ 
at 480V
MOP² (amps) 
at 480V
Actual kW & 
BTU at 480V
Recommended
Airflow Range
CPC036***4B***
10
15
EHK4-10
17
20
10
1250-1350 CFM
EHK4-15
25
25
15
1400-1440 CFM
Model and 
Heat Kit Usage
MCA¹  
at 575V
MOP² (amps) 
at 575V
Actual kW &  
BTU at 575V
Recommended
Airflow Range
CPC036***7B***
8
15
EHK7-10
15
20
10
1250-1350 CFM
EHK7-15
22
25
15
1400-1440 CFM
¹   Minimum Circuit Ampacity
²   Maximum Overcurrent Protection device
Minimum Airflow for Electric Heat
Heater Size
Minimum CFM
A Models
B Models
10 kW
1,250
1,250
15 kW
1,400
1,250