Hoshizaki KM2000SWF3 Benutzerhandbuch
16
4. Defrost Timer stops counting.
Defrost cycle is completed and freeze cycle
starts.
Defrost cycle is completed and freeze cycle
starts.
[c] SEQUENCE
1st Cycle [KM-2000SWF3, KM-2000SRF3, KM-2000SWH3 and KM-2000SRH3]
1. Unit energized and Control Switch to “ICE”
position. Water supply cycle starts.
position. Water supply cycle starts.
2. After 1 minute.
Defrost cycle starts.
Defrost cycle starts.
IMPORTANT
Water Valve
opening is limited
to 6 minutes.
opening is limited
to 6 minutes.
5. After the first 5 minutes in freeze cycle.
Ready to complete freeze cycle when Float
Switch circuit opens.
Ready to complete freeze cycle when Float
Switch circuit opens.
IMPORTANT
1. Board never accepts defrost completion signal
within the first 2 minutes in defrost cycle.
within the first 2 minutes in defrost cycle.
2. Defrost cycle time is limited to 20 minutes even
if Defrost Timer does not stop counting.
if Defrost Timer does not stop counting.
3. Thermistor reads 48°F.
Defrost Timer starts counting.
Defrost Timer starts counting.
IMPORTANT
Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.
within the first 5 minutes in freeze cycle.