Hoshizaki KM2000SWF3 Benutzerhandbuch

Seite von 56
19
DIP SWITCH NO.
1
2
3
4
5
6
7
8
9
10
                         
        OFF   OFF     ON       ON       ON      ON   OFF     OFF      OFF    OFF
[d] CONTROLS AND ADJUSTMENTS
The Dip Switch is factory-adjusted to the following positions:
Switch Nos. 1 and 2:
Used for adjustment of the Defrost Timer.
The Defrost Timer starts counting when the Thermistor reads a certain temperature
           at the Evaporator outlet.
Switch Nos. 3 and 4:
Used for adjustment of the Drain Timer.
When a freeze cycle is completed, the Pump Motor stops, and the icemaker
           resumes operation in 2 seconds.  Then the Pump Motor drains the Water Tank
           for the time determined by the Drain Timer.  The Drain Timer also determines the
           time to restrain completion of a defrost cycle, i.e. the minimum defrost time.
Switch Nos. 5 and 6:
 Used for adjustment of the Drain Counter.
  The Pump Motor drains the Water Tank at the frequency determined by the Drain
            Counter.
Switch Nos. 7 and 8:
            Used only for checking the Controller Board.  Usually set in OFF position.
Switch Nos. 9 and 10:
Used for adjustment of Freeze Timer.
The Freeze Timer determines maximum
freeze cycle time.  Upon termination of
Freeze Timer, machine initiates the
harvest cycle.  After 2 consecutive timer
terminations, machine will shut down,
possibly indicating a problem.
KM-2000S_F3,
KM-2000S_H3