Hoshizaki KM2000SWF3 Benutzerhandbuch

Seite von 56
35
  PROBLEM
         POSSIBLE CAUSE
 REMEDY
[1] Icemaker will
a) Bin Control
1. Set too cold.
1. Adjust warmer.
     not stop when
    Thermostat
2. Defective.
2. Replace.
     bin is filled
     with ice.
[2] Abnormal
a) Pump Motor
1. Bearings worn out.
1. Replace.
     noise
b) Fan Motor
1. Bearings worn out.
1. Replace.
2. Fan blade deformed.
2. Replace fan blade.
3. Fan blade does not move
3. Replace.
    freely.
c) Compressor
1. Bearings worn out, or
1. Replace.
    cylinder valve broken.
2. Mounting pad out of
2. Reinstall
    position.
d) Refrigerant Lines
1. Rub or touch lines or other
1. Replace.
    surfaces.
[3] Ice in storage
a) Bin Drain
1. Plugged.
1. Clean.
     bin often
b) Icemaker and Bin
1. Drains not run separately.
1. Separate the Drain Lines.
     melts.
5. OTHERS
4.  ABNORMAL ICE
  PROBLEM
         POSSIBLE CAUSE
 REMEDY
[1] Small Cube
a) Ice Cube Guide
  1. Out of position.
1. Place in position.
                Circulated water falls into
      bin.
b) See chart 1 - [5], and check water supply line, Water Solenoid Valve, water system,
     Pump Motor or Controller Board.
c) Pump Out Check Valve  1. Dirty.
1. Clean.
[2] Cloudy or
a) See chart 2 - [1] and - [3], and check Float Switch, Water Solenoid Valve,
      irregular cube      Controller Board, Spray Tubes, water system, refrigerant charge or Expansion
     Valve.
b) Spray Guide
   1. Dirty.
1. Clean.
c) Water Quality
   1. High hardness or contains 1. Install a water filter or
       impurities.
              softener.
3.  LOW ICE PRODUCTION
  PROBLEM
         POSSIBLE CAUSE
 REMEDY
[1] Freeze cycle
a) See chart 1 - [3], and check dirty Air Filter or Condenser, ambient or water
     time is long.
     temperature, water pressure, Water Regulator or refrigerant charge.
b) See chart 2 - [1], and check Float Switch, Water Solenoid Valve or Controller
     Board.
[2] Harvest cycle
a) See chart 2 - [2], and check Controller Board, Thermistor, Evaporator, ambient
     time is long
     and/or water temperature, water supply line, Water Solenoid Valve, Line Valve,
     or Hot Gas Valve.