G. Diagnostic Charts
Before consulting the diagnostic charts, check for correct installation, proper voltage per unit 
nameplate, and adequate water supply. Check CB using the steps in "IV.B. Control Board
Check." Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, & 10 and
S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5, & 6 are 
cleaning adjustments and the settings are flexible. For factory default settings, see "II.C.3.a)
Default Dip Switch Settings."
1. No Ice Production
No Ice Production - Possible Cause
1. Power Supply
a) Off, blown fuse, or tripped breaker.
b) Not within specifications.
2. Main Transformer (230V/115V)
a) Coil winding open or shorted.
3. Water Supply
a) Water supply off or improper water pressure.
b) External water filters clogged.
4. Thermostatic Bin Control. 
See "IV.C.1. Thermostatic Bin
Control Check."
a) Tripped with bin filled with ice.
b) Ambient temperature too cool.
c) Set too warm.
d) Bulb out of position.
e) Bad contacts.
5. Fuse (Control Box)
a) Blown.
6. Control Switch
a) Bad contacts.
7. High-Pressure Switch
a) Bad contacts.
b) Dirty air filter or condenser.
c) Ambient or condenser water temperature too warm.
d) Refrigerant overcharged.
e) Fan not operating (air-cooled and remote air-cooled models).
f) Refrigerant lines or components plugged.
g) Condenser water pressure too low or off (water-cooled model).
h) Headmaster (C.P.R.) open (remote condenser unit).
8. Control Transformer 
(115V/10.5V)
a) Coil winding open or shorted.
9. Control Board
See "IV.B. Control Board Check."
a) In alarm.
b) Defective.
10. Mechanical Bin Control
See "IV.C.2. Mechanical Bin
Control Check and Cleaning."
a) Tripped with bin filled with ice.
b) Actuator does not move freely.
c) Defective.
11. Thermistor
See "IV.E. Thermistor Check."
a) Leads shorted or open.
12. Hot Gas Valve
a) Open in freeze cycle. 
b) Closed in harvest cycle.
13. Inlet Water Valve
a) Mesh filter or orifice clogged.
b) Coil winding open.
c) Open in freeze cycle.