MX410/MX412 System Manual
iv
 PRELIMINARY
61189500L1-1B
Compliance
The MX410 (P/N 1189500L1) and MX412 (P/N 1189512L1) comply with the requirements 
covered under UL 60950 and NEBS Level 3. The MX410 and MX412 are intended to be 
installed in a restricted access area only.
The MX410 and MX412 devices comply with Part 15 of the FCC Rules. Operation is subject to 
the following two conditions:
1. The device may not cause harmful interference.
2. The device must accept any interference received, including interference that may cause 
undesired operation.
Changes and modifications not expressly approved by ADTRAN could void the user’s authority 
to operate this equipment.
WARNING
The V.35, Ethernet, terminal server, craft port, and FXS port (if
present) interfaces are not to be connected to outside plant (OSP)
facilities.
CAUTION
Per GR-1089-CORE October 2002, Section 9, this system is
designed and intended only for installation in a DC-C (common)
Bonding and Grounding system. It is not intended or designed for
installation in a DC-I (isolated) Bonding and Grounding system.
The ground wire must be of equal or greater ampacity than the wire
connected to the VDC return.
The Compliance Codes for the MX410/MX412 units and the MX410 Power Supply Unit (PSU) 
are provided in the following tables.
Table 1.  MX410 and MX412 Compliance Codes
Code
Input
Output
Power Code (PC)
F
C
Telecommunication Code (TC)
X
X
Installation Code (IC)
A
Table 2.  MX410 Power Supply Unit Compliance Codes
Code
Input
Output
Power Code (PC)
F
C
Telecommunication Code (TC)
Installation Code (IC)
A