Quantum p1000 Betriebsanweisung
Chapter 5 Service Commands
Testing the Library
Testing the Library
80
ATL P1000 Series User’s Guide
Procedure (continued)
3
Select all desired test options:
•
To swap cartridges randomly, press the Random button.
If you do not press this button, cartridges are swapped
sequentially from the first bin or drive.
sequentially from the first bin or drive.
•
To have the library read the bar code as it swaps each cartridge,
press the Use Barcodes button.
press the Use Barcodes button.
•
To have the test run continuously until aborted, press the
Continuous button. Otherwise, enter the number of times you
want the test to run into the # of Runs box.
Continuous button. Otherwise, enter the number of times you
want the test to run into the # of Runs box.
4
When you have selected the test and all test options, press the
Execute button.
Execute button.
The GUI displays a “Command In Progress” screen.
To cancel the system test, press the Abort button.
Note: If you selected the Continuous option in step 3, you must press
the Abort button to stop the test.
Performing a Service
Calibration
Calibration
5
The Service Calibrate command autocalibrates the library (the tape
drives, the cartridge bins, and the load port) and saves the target
locations as a baseline for all subsequent calibration procedures.
drives, the cartridge bins, and the load port) and saves the target
locations as a baseline for all subsequent calibration procedures.
Note: Before performing a service calibration, remove all tape cartridges
from the library.
To perform a service calibration, press the Calibrate Library button on
the Service screen. The GUI displays a “Command In Progress” screen
during the calibration process.
the Service screen. The GUI displays a “Command In Progress” screen
during the calibration process.
To cancel the calibration process, press the Abort button.