Rack Mounting the Switch
SecureStack A2 Installation Guide 3-9
If you are installing several switches in a stack, proceed to “
” on page 3‐15 for power connection instructions.
Figure 3-5 Area Guidelines for Switch Installation on Flat Surface
Rack Mounting the Switch
To install the switch in a 19‐inch rack, you need:
•
Two rackmount brackets and mounting screws (rackmount kit) shipped with the
switch.
switch.
•
Four user‐supplied screws to attach the switch to a standard 19‐inch rack.
Caution: To ensure proper ventilation and prevent overheating, leave a minimum
clearance space of 5.1 cm (2.0 in.) at the left, right, and rear of the switch.
clearance space of 5.1 cm (2.0 in.) at the left, right, and rear of the switch.
Do not connect the switch to the AC power source until instructed to do so later in the
installation process.
installation process.
Precaución: Para asegurar una buena ventilación y evitar que el sistema se
sobrecaliente, deje un espacio mínimo de 5.1 cm (2 pulgadas) con respecto a los lados y
a la parte posterior del aparato.
sobrecaliente, deje un espacio mínimo de 5.1 cm (2 pulgadas) con respecto a los lados y
a la parte posterior del aparato.
No conecte el dipositivo a la fuente primaria hasta que no se le indique.
1 Approximately 152 cm (5 ft) from power source
3 44.5 cm (19.4 in.) for proper ventilation
2 4.45 cm (1.75 in.) per switch. (Vertical clearance
depends on number of switches stacked.)
4 41.9 cm (16.5 in.) for proper ventilation