Chapter 3: 6C105 Setup
3-12
6C105 Overview and Setup Guide
Figure 3-6
Power Supply DC ON/OFF Switch and DC Input Power Strip
DC Power Supply Requirement for Each Supply
Each DC power supply input requires either a 48 VDC or 60 VDC power 
source, rated at a minimum of 17 Amps.
ONLY QUALIFIED PERSONNEL SHOULD PERFORM THESE 
INSTALLATION PROCEDURES.
TO REDUCE THE RISK OF ELECTRIC SHOCK OR ENERGY 
HAZARDS:
CONNECT TO A RELIABLY GROUNDED 48/60 VDC 
SELV SOURCE.
ENSURE THE BRANCH CIRCUIT OVERCURRENT 
PROTECTION IS RATED AT A MINIMUM 
OF 25 A.
USE 10 AWG SOLID COPPER CONDUCTORS ONLY.
ENSURE THAT A READILY ACCESSIBLE 
DISCONNECT DEVICE THAT IS SUITABLY 
APPROVED AND RATED, IS INCORPORATED IN 
THE FIELD WIRING.
TO BE INSTALLED IN A RESTRICTED ACCESS AREA IN 
ACCORDANCE WITH THE NEC OR THE AUTHORITY 
HAVING JURISDICTION.