Fortinet fortigate-5001a Hardwarehandbuch

Seite von 97
FortiGate-5140 chassis 
Connecting the FortiGate-5140 chassis to AC power using the FortiGate-5053 power converter tray
FortiGate-5000 Series   Hardware Guide
01-00000-0293-20060315
23
Connecting a FortiGate-5140 chassis to the FortiGate-5053 power converter 
tray
To use a FortiGate-5053 power converter tray with the FortiGate-5140 chassis 
you need to make DC power connections between the FortiGate-5140 chassis 
and the FortiGate-5053 power converter tray. You also need to the connect the 
FortiGate-5140 chassis to Data Center ground.
If you are connecting both PEMs and connecting multiple power zones, the 
-48VDC and RTN terminals on PEM A and PEM B must be wired symmetrically. 
See 
 for information about 
FortiGate-5140 power zones.
To connect a FortiGate-5140 PEM to a FortiGate-5053 power converter tray
Each PEM includes four connectors that connect power to four different power 
zones in the FortiGate-5140 chassis. Each power zone supplies power to different 
FortiGate-5140 slots and cooling fan trays. Power can be connected in a number 
of configurations depending on the requirements of a particular installation. The 
following procedure describes how to connect power to power zones 3 and 4 of 
one PEM.
You need the following tools and equipment to connect a FortiGate-5140 PEM to 
a FortiGate-5053 power converter tray:
A number 2 Phillips screwdriver.
An electrostatic discharge (ESD) preventive wrist or ankle strap with 
connection cord.
The required number of red and black AWG-14 stranded wires with terminal 
lugs attached.
A FortiGate-5053 power converter tray containing two or three FortiGate-5140 
power supplies and mounted in a rack near the FortiGate-5140 chassis.
Figure 11: Connect a FortiGate-5140 PEM to a FortiGate-5053 power converter tray
V-
24 VAC   1    2    3
V-
(Black)
(RTN)
(Red)
1
2
3
4
1
2
3
4
HS
HS
operate
Alarm
-48V/-60 VDC nom
RTN
1
2
3
4
1
2
3
4
RTN (positive)
terminal strip
connectors
1, 2, 3, 4
RTN Red to
FortiGate-5053
RTN
-48V/-60 VDC
terminal strip 
connectors 
1, 2, 3, 4
-48V/-60 VDC Black to
FortiGate-5053
-48/-58 VDC
-48V
RTN
AC in