Eaton IPC3601 Benutzerhandbuch
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
2
IPC36XX- Front
CB
IPC3601 Rear
IPC3602 Rear
CHASSIS
•
1.72” (1U) x Depth 9.5” x Width 19.0”
•
Weighs approximately 12 lbs.
•
Powder coated black steel
•
Detachable mounting brackets allow for
several mounting options
several mounting options
NEMA or IEC 320 OUTLETS
•
IPC3601 has 8 IEC 60320 Type
C13 (computer style) outlets
C13 (computer style) outlets
•
IPC3602 has 8 NEMA 5-15R
(3 prong) outlets
(3 prong) outlets
12 INDICATOR LIGHTS
•
Main power system on
•
Power “on” to outlets 1-8
•
2 Data and ethernet link
POWER INPUT
•
IEC 60320 Type C20 Inlet
•
Mating power cables must be
ordered separately
•
IPC3601 has a full range power
supply for use at 100-240V
EMI/RFI FILTERING
•
Common Mode - Line to Ground
•
Differential Mode - Line to Line
•
Filtered inlet isolates noise before
entering the system
•
IPC3601-F3-3316 –
NO FILTER
SPIKE/SURGESUPPRESSION
•
Line to Neutral (or Line)
OVERLOAD PROTECTION
•
Push button circuit breaker pops out
when an overload occurs
•
Push to reset
SOFTWARE SECURITY
•
User name/password security
•
Settings allow the administrator to
disable unused interfaces
SERIAL/ETHERNET
•
Serial RS232 via RJ22 connector on the
rear. 6’ RJ22 to DB9 cable included
rear. 6’ RJ22 to DB9 cable included
•
Serial baud rate is 9600 default or
38,400 maximum
•
Ethernet (10/100) network via RJ45
connector on the rear. 6’ network
cable included
cable included
•
Network setup allows DHCP or any
static public/private IP address
SOFTWARE INTERFACES
•
Web interface provides a graphic
control interface through a web
browser (IE, Netscape, Mozilla)
•
Telnet interface provides a text menu
control interface with any terminal
control interface with any terminal
emulation software
•
SNMP allows read/write capability
with trapping
•
E-mail notification system provides e-mail
alerts or logs showing user activity
alerts or logs showing user activity
•
Serial interface provides a text menu
control interface with any terminal
control interface with any terminal
emulation software
•
FTP utility allows firmware upgrades
SOFTWARE FEATURES
•
Administrator and multiple users can
be configured
be configured
•
User level access can be limited to
specific outlets
•
Unit and outlet names can be configured
•
Outlet groups can be created to
perform an action on multiple outlets
•
Outlet control includes individual,
group and all outlet global control
•
Outlet actions include on or off and reboot
•
Global sequence allows all the
outlets to be turned on or off in a
preset sequence up to 999 seconds
•
Outlet reboot automatically turns an outlet
off and back on with one command at a
preset time up to 999 seconds
off and back on with one command at a
preset time up to 999 seconds
•
E-mail notification allows up to two
e-mail addresses to receive notifications
of alerts or events
of alerts or events
AUTO-EVENT SCHEDULING
•
Administrator can configure on or off
events for outlets or groups. The event
occurs at the preset time daily or weekly
events for outlets or groups. The event
occurs at the preset time daily or weekly
SPECIFICATIONS
IPC3601
IPC3602
IPC3601-F3-3316
Approvals
CB, CE, UL/cUL Listed, FCC UL/cUL Listed, FCC
NA
Voltage Input/Output (50/60Hz)
100-240V~
120V~
200-240V~
Current Rating
16A
16A
24A
Full Load VA
1920VA @ 120V~
3840VA @ 240V~
3840VA @ 240V~
1920VA
5760VA
Ethernet/Serial
YES
YES
YES
Outlets
IEC C13
NEMA 5-15R
IEC C13
Circuit Breaker
20A
20A
(2) 15/15A
EMI/RFI Filter
20A
20A
NO
Surge Suppression
YES
YES
YES
Power Input
C20 Inlet
C20 Inlet
Attached
Power Cable/Plug
Not Included
Not Included
10’ - L6-30P