Free Access Underfloor Connection of Power Cable 
If the height of underfloor is less than 300mm (11.8 in.), the power distribution is set to sideways. 
FIGURE 2.12 When Underfloor Height is less than 300mm (11.8 in) 
 
 
Number 
Description 
(1) 
Free access floor 
(2) 
Less than 300mm (11.8 in) 
(3) 
Recipient power distribution  
 
The connector format and cable bend radius of power cable are considered at the time of connecting the 
power cable of power distribution box (or base cabinet) under the free access floor. It is recommended that 
the under floor height is 300 mm (11.8 in) or more. 
The recipient power distribution should be arranged near the device. 
FIGURE 2.13 When the under floor height is 300 mm (11.8 in) or more. 
 
 
Number 
Description 
(1) 
Free access floor 
(2) 
200 mm (9.8 in) 
(3) 
300 mm (11.8 in) or more 
(4) 
Recipient power distribution 
Remarks 
The above figure shows an example of 19-inch rack mounted with the device. 
 
2.5 
Cutoff Characteristics of Distribution Panel (At the time 
of connecting power distribution box) 
At the time of connecting the distribution panel through power distribution box, protection should be 
coordinated so that the breaker of the device (or power distribution box) trips before the breaker of the 
distribution panel trips. Such protection should be maintained. Therefore, the distribution panel should have 
the characteristic conditions sh
own in “
It is necessary to use Distribution panel Breaker suitable to these conditions.