Cisco Cisco C880 M4 Server Installationsanleitung

Seite von 134
47 
CA92344-0879-01 
 
APP0100000 
Customer's Distribution Panel Breaker Requirements 
(Only When Connected to a Power Distribution Box) 
 
This appendix describes the requirements for the breaker in the customer's distribution panel. 
 
To protect the device when it is connected to the customer's distribution panel through a power   
distribution box, the corresponding breaker in the customer's power distribution panel must meet   
the following characteristic requirements so that the breaker of the device (or the power distribution   
box) trips before the corresponding breaker in the customer's distribution panel. Use a breaker that   
meets these requirements in the customer's distribution panel. 
Table A.1 
Power input 
Device name 
Capacity of breaker in 
customer's distribution panel 
  (for use in countries other than 
European countries) 
Capacity of breaker in 
customer's distribution 
  panel (for use in Europe) 
200 to 240 VAC 
Power distribution   
box 
30A 
32A 
 
Use a long-time-delay type breaker whose characteristics correspond to phase D shown in Figure   
A.1 Breaker characteristics (IEC898 or DIN0641 Part II). Alternatively, use a slower breaker. 
 
Figure A.1 Distribution panel breaker characteristics