  Technical Specifications 
Environmental Specifications  ▀   
 
ASR 5500 Installation Guide  ▄  
 
   
29 
Environmental Specifications 
The ASR 5500 is designed for deployment in unattended sites equipped with redundant power systems, redundant data 
communications connections, environmental controls (air conditioning, fire suppression), security devices and 
controlled access. 
Environmental Parameters 
The table below lists the environmental parameters (operating and storage) for the ASR 5500 chassis. 
Table 4.  Environmental Parameters 
Parameter
 
Subparameter
 
Range
 
Temperature
 
Operating
 
0 degrees C to +40 degrees C (32 degrees F to 104 degrees F)
 
Short Term 
 
-5 degrees C to +50 degrees C (23 degrees F to 122 degrees F)
 
Storage
 
-40 degrees C to +70 degrees C (-40 degrees F to 158 degrees F)
 
Humidity
 
Operating
 
20 to 80 percent non-condensing
 
Storage
 
10 to 95 percent non-condensing
 
Altitude
 
Operating
 
197 ft. (60m) below to 5,905 ft. (1,800m) above sea level, maximum 
40 degrees C (104 degrees F)
 
5,905 ft. (1,800m) to 13,123 ft. (4000m) above sea level, maximum 
30 degrees C (86 degrees F)
 
Non-operating
 
197 ft. (60m) below to 49,212 ft. (15,000m) above sea level
 
Acoustic Noise
 
23 degrees C (73.4 degrees F)
 
81 dB (within GR-63 limits for unattended operation)
 
27 degrees C (80.6 degrees F)
 
81 dB (within GR-63 limits for unattended operation)
 
Max. Fan Speed
 
96 dB (as measured during GR-63 R4-97 testing)
 
 
Notes
1.  Short-term refers to a period of not more than 96 consecutive hours and a total of not more than 15 days in 1 
year. (This refers to a total of 360 hours in any given year, but no more than 15 occurrences during that 1-year 
period.)