Power Requirements ▀
ASR 5500 Installation Guide ▄
35
Important:
The DC power BR input terminal of the ASR 5500 is not connected to the equipment frame (chassis)
and is configured as DC-I in compliance with GR-1089-CORE (sec.9.8.3).
Example Power Calculations
DPC/UPDC Full Chassis
This calculation assumes that a fully redundant ASR 5500 chassis will be equipped with DPC/UDPCs.
(8) DPC/UDPCs [8x630w] = 5040 watts
(2) MIO/UMIOs [2x650w] = 1300 watts
(4) FSCs [4x150w] = 600 watts
(2) SSCs [2x10w] = 20 watts
Fan Units [front and rear] = 2000 watts
Total = approximately 9 kW
DPC2/UDPC2 Full Chassis
This calculation assumes that a fully redundant ASR 5500 chassis will be equipped with DPC2/UDPC2s.
(8) DPC2/UDPC2s [8x760w] = 6080 watts
(2) MIO/UMIOs [2x650w] = 1300 watts
(4) FSCs [4x150w] = 600 watts
(2) SSCs [2x10w] = 20 watts
Fan Units [front and rear] = 2000 watts
Total = approximately 10 kW