Troubleshooting   
▀  Detecting Faulty Hardware 
 
 
▄  ASR 5000 System Administration Guide, StarOS Release 18 
206 
   
Detecting Faulty Hardware 
When power is applied to the chassis, power is sequentially applied to management cards, application cards and line 
cards. 
Each PFU, application and line card installed in the system incorporates light emitting diodes (LEDs) that indicate its 
operating status. This section describes how to use these status LEDs to verify that all of the installed components are 
functioning properly. 
Important:
  As the system progresses through its boot process, some cards will not exhibit immediate LED 
activity. Allow several minutes to elapse after a reboot is initiates before checking the LEDs on the various cards to 
verify that the boot process has successfully completed. 
Using the CLI to View Status LEDs 
The status of application and line card LEDs can be viewed through the CLI by entering the show leds all command in 
Exec mode. 
[local]host_nameshow leds all 
The following displays a sample of this command’s output. 
Slot 01: Run/Fail: Green       | Active:  Off         | Standby: Green 
Slot 08: Run/Fail: Green       | Active:  Green       | Standby: Off 
         Status:   Green       | Service: Off         |  
Slot 09: Run/Fail: Green       | Active:  Off         | Standby: Green 
         Status:   Green       | Service: Off         |  
Slot 12: Run/Fail: Green       | Active:  Green       | Standby: Off 
Slot 14: Run/Fail: Green       | Active:  Green       | Standby: Off 
Slot 17: Run/Fail: Green       | Active:  Green       | Standby: Off 
Slot 24: Run/Fail: Green       | Active:  Green       | Standby: Off 
Slot 25: Run/Fail: Green       | Active:  Off         | Standby: Green 
Slot 30: Run/Fail: Green       | Active:  Green       | Standby: Off 
Slot 33: Run/Fail: Green       | Active:  Off         | Standby: Off 
Slot 40: Run/Fail: Green       | Active:  Green       | Standby: Off 
The status of the two Power Filter Units (PFUs) can be viewed by entering the show power chassis command in the 
Exec mode.