Zigor RHIN PLUS 6KVA 18631 Merkblatt
Produktcode
18631
Specifications may be changed without notice
TECHNICAL SPECIFICATIONS
Rhin Plus series
Power kVA
6
10
General
Technology
Technology
Digital On-Line, double conversion, parallel
Overload
Inverter supply: up to 150% for up to 160 sec depending on load
Bypass supply: up to 200% for up to 500sec depending on load
Input
Acceptable Input voltage range
Acceptable Input voltage range
(single phase)
160~280 Vac
Acceptable frequency
45~65Hz
Phase / Wire
Single line + neutral+ ground
Power factor
Up to 0.99 at 100% linear load
Current THD (100% linear load)
<6% (100% linear load)
Output
Power (Va/W)
Power (Va/W)
6000/4200
10000/7000
Voltage (normal mode)
200/208/230/240Vac (selectable (208/120Vac optional))
Output frequency
±1Hz±3Hz
Output type
Screw terminals - for hard wiring facility
Wave form
Sinewave, total harmonic distortion <3% (no load to full load)
Efficiency AC to AC
Up to 90% (normal), (ECO: up to 95%)
Crest factor
3:1
Batteries & Autonomy
Standard battery
Standard battery
Pb VRLA Sealed lead acid maintenance free
Autonomy (full load)
8 min (External Battery Pack)
5 min (External Battery Pack)
Charge time
4 hours to 90%
Capacity
12V/7Ah
12V/9Ah
Voltage
240Vdc
Model BBC20J0007 (018609)
7AH / 80pcs / 18/Kgs (w/o batteries) / 68.0/Kgs / 440x132x680 mm
Model BBC20N0009 (018610)
9AH / 80pcs / 18/Kgs (w/o batteries) / 68.0/Kgs / 440x132x680 mm
Controls
LEDs & Acoustics
LEDs & Acoustics
Line failure, System fault conditions, Overload, Low battery, Transfer to by-pass
Communication
Standard interface RS232
Standard interface RS232
Input/output voltage Frequency / Temperature / Charge level Battery level
SNMP Internal card (optional)
Historic events/ System analysis
Input/Output connection
Hardwire facility
External battery connection
Plug & play
Communication slots
2nd RS232,USB,RS485, Relay contact, SNMP/WEB Card, etc (optional)
Protection
Current limitation
Current limitation
Yes
Static by-pass/ manual
Yes / optional
RFI filter
Yes
Frequency
45~65Hz
PFC: Power factor corrector
Battery charger protector
Yes
Display
On LCD+LED: Line mode,back-up,ECO mode,Bypass supply, Battery low/bad/disconnect, Overload Transfering
with interruption and UPS fault
On LCD: Input voltage/frequency, output voltage/frequency, load percentage, battery voltage & inner temperature
Self diagnostics
Upon Power-on, Front panel setting & software control, 24 hour routine checking
CE Certificates
Norms/Certificates
Norms/Certificates
ISO Certificate , EN 62040-1-1:2003, UL1778, EN 62040-2, EN 61000-3-2, EN 61000-3-3, FCC class A, CE, cUL, UL
Additional features
Operation temperature
Operation temperature
>0-40ºC / 32 to 104ºF
Relative Humidity
90% RH maximum (non condensing)
Altitude without decreasing
power
2000 ASL (above sea level)
Acoustic level
<50dBA
Dimensions (mm)
440x88x680
440x132x680
Weight (kgs)
24.0 - No batteries in UPS
26.0 - No batteries in UPS
207ENFW00