5
Battery run times and recharge times
Table 3 lists the expected period that the 6000VA UPS will operate solely on batteries. The run times for 
the 230V model are the same as the 200/208V model.
Table 3. IBM 6000VA UPS runtime chart
Load
Run time on batteries
Percent Load
VA
Watts
Run time with standard internal  
battery only
Run time with internal battery plus  
External Battery Module  (EBM)
25%
1500
1400
51 minutes
112 minutes
50%
3000
2800
21 minutes
51 minutes
75%
4500
4200
12 minutes
31 minutes
100%
6000
5600
8 minutes
19 minutes
Note: Battery backup times are approximate and may vary with equipment, configuration, battery age, 
and temperature.
Physical specifications
The physical specifications of the 4U uninterruptible power supply are as follows:
Height: 172 mm (6.8 in.)
Width: 483 mm (19 in.)
Depth: 735 mm (28.9 in.)
Weight: 72 kg (159 lb)
The physical specifications of the 3U Extended Battery Module are as follows:
Height: 127 mm (5.0 in)
Width: 483 mm (19 in.)
Depth: 721 mm (28.4 in.)
Weight: 59 kg (130 lb)
Operating environment
The IBM 6000VA LCD 4U Rack UPS is supported in the following environment:
Maximum operating altitude: 3,048 m (10,000 ft)
Maximum storage altitude: 15,240 m (50,000 ft)
Operating temperature at 0 to maximum altitude: 0°C to 40°C (32°F to 104°F)
24-hour transport storage temperature at 0 to maximum storage altitude: -15°C to 60°C (5°F to 140°F)
Extended storage temperature at 0 to maximum storage altitude: -15°C to 45°C (5°F to 113°F)
Relative humidity: 0 to 95% noncondensing
Warranty