Samsung AQV12PSBX Benutzerhandbuch

Seite von 45
28
Wall
<20mm
Plastic 
Anchor
Fixing the installation plate
2.  Fix the indoor unit.
If you fix the indoor unit on a wall 
(1)   Fix the installation plate to the wall giving attention to the weight of the indoor unit. 
If you fix the indoor unit on a window frame 
(1)   Determine the positions of the wooden uprights to be 
attached to the window frame. 
(2)   Attach the wooden uprights to the window frame giving 
attention to the weight of the indoor unit.
(3)   Attach the installation plate to the wooden upright using 
tapping screws.
If you fix the indoor unit on a gypsum board 
(1)   Use stud finder to find out locations of the studs. 
(2)  Fix the plate hanger on two studs.
•   If you mount the plate to a concrete wall using plastic anchors, make sure that
gaps between the wall and the plate, created by projected anchor, is less than 
20mm.
•   Search for other spots if there are less than two studs, or the distance between the studs are different from the
plate hanger.
•  Fix the installation plate without inclining to one side.
•   Make sure that a wall can withstand the weight of the product. If you install the product in a place where it is not
strong enough to withstand the product weight, the unit could fall and cause injury.
Connecting the assembly cable
•   Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to
the power supply, it must be incorporated in a wire with a contact opening of ≥3mm.
Model
Power cable
Interconnection cable
Type GL 
AQV09/12PA
3G, 1.5mm
² H07RN-F
4G, 1.5mm
² H07RN-F
20A
AQV09/12PB
3G, 2.5mm
² H07RN-F
3G, 1.5mm
² H07RN-F
20A
2* 0.75mm
² H05RN-F
AQV18/24P
3G, 2.5mm
² H07RN-F
3G, 1.5mm
² H07RN-F
25A
2* 0.75mm
² H05RN-F
Cable specification
Connecting the cable
If using a multi system, install as described in the installation manual supplied with the outdoor unit.
Electrical work 
(1)   For electrical and earth works, comply with the ‘technical standards of electrical installations’ and the the wiring 
regulations’ of the Electricity Enterprises Act.
(2)   Tighten the terminal block screw to under 12kgf.cm.
(3)   Precautions when connecting terminal blocks of the indoor unit
  Before connecting, make sure the connecting part of the terminal socket is facing upwards.
Upside down
The terminal 
socketis damaged.
There is no ring 
terminalto cover the wire.