AEG 1000 Benutzerhandbuch

Seite von 76
 
 
66 
 
Fig. 22
 
: Removing the UPS front cover 
6.  Disconnect the internal battery connector and EBM battery 
connector. If the EBM cable is not connected to an EBM, 
unclip the EBM cable and move it to the left out of the way, 
see Figure 23. 
7.  Remove and retain the two screws on the battery cover 
plate, see Figure 23. 
 
Fig. 23
 
:  Disconnecting the UPS internal batteries; 
  
Removal of the battery cover plate  
8.  Grasp an edge of the battery cover plate and pull it out 
gently. Remove and retain the battery cover plate. Figure 23 
shows the location of the battery cover plate. 
Carefully pull the handle on the battery tray and slide the 
battery package slowly out onto a flat, stable surface; use 
two hands to support the battery package, see Figure 24. 
Pay attention to the weight of the battery system, especially 
at the more powerful models. 
This part stays 
in the rack! 
3