act actpro product range Benutzerhandbuch

Seite von 1
The above diagram is valid only
for clock-and-data type readers.
ACT1050 Pin and Proximity
Reader (Entry)
ACT1030 Proximity
Reader (Exit)
Wire both readers in parallel but leave 
the SENSE line on  the Exit reader unconnected.
Controller
Sense
Clock
Data
+5v
0v
Red Led
Grn Led
C
ard
/P
ro
x R
ea
de
r
2
3
1
5
6
4
8
9
7
0
Wiring for Entry/Exit Readers
White
Green
Blue
Red
Black
Brown
Yellow
Orange
Sense
Clock / Data1
Data  / Data 0
+5v
0v
Red Led
Grn Led
(Buzzer Ctrl)
Wiring for Clock and Data / Wiegand Reader
The +5V reader supply on ACT controllers is normally rated 
at 100mA. Typically this is sufficient to power 2 ACT readers. 
Note however that readers from other manufacturers may need 
to be powered separately if their current requirements exceed 
this or if they require 12V.
The standard wiring colours for
ACTPro Proximity and Pin readers
is shown above. Readers 
should be a maximum of 30m
from the controller when powered 
from +5V and a maximum of 100m
when powered from +12V.
OM
RO
N
5A
 2
50
VA
C
5A
 3
0V
DC
OM
RO
N
1A
 12
5V
AC
1A
 30
VD
C
5-12V dc
 
0V
0  1  2  3  4  5  6  7  8  9 
B A T C H:
P R ODUC T :
S E R IA L   NUMB ER :
02X X -1
AC T P ro R E V 1.3
00X X X X
Data / D0
 
C lock / D1
 
Sense
 
R ed L E D
 
Grn L E D
 
B uzz C trl
 
Internal buzzer is 
activated by applying 
0V to Buzz Ctrl
Rear view of ACTPro 1040/1050/1060
connected to the ACT2000/1000/DS100
ACTPro Product Range 
1030/1040/1050/1060   
For Wiegand readers .
Wire both readers in parallel but connect D0
line of the exit reader into the SENSE line on 
the controller,leave the SENSE line on  the
Exit reader unconnected.
Unit 8 Tallaght Business Centre, W hitestown, Tallaght, Dublin 24, Ireland. 
Telephone: 353 1 462 2585.  Telefax: 353 1 462 2587. E-mail: sales@ accesscontrol.ie  W eb: www.accesscontrol.ie