Juniper CBL-M40-PWR-AU Benutzerhandbuch

Seite von 268
Safety Guidelines and Warnings
M40 Internet Router Hardware Guide
62
„ You must connect only to a DC power source for which the output complies with the 
safety extra low-voltage (SELV) requirements of UL 1950, CSA C22.2 No. 950-95, EN 
60950, and IEC 60950 to a DC-input terminal block. 
„ A DC-powered router that is equipped with a DC terminal block is intended only for 
installation in a restricted access location. In the United States, a restricted access area is 
one in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical 
Code ANSI/NFPA 70.
„ Ensure that the polarity of the DC input wiring is correct. Under certain conditions, 
connections with reversed polarity might trip the primary circuit breaker or damage the 
equipment.
„ For personal safety, connect the green and yellow wire to safety (earth) ground at both 
the router and the supply side of the DC wiring.
„ The marked input voltage of –48 VDC for DC-powered routers is the nominal voltage 
associated with the battery circuit, and any higher voltages are only to be associated 
with float voltages for the charging function. 
„ Because the router is a positive ground system, you must connect the positive lead to the 
terminal labeled 
RTN(+)
, the negative lead to the terminal labeled 
–48V
, and the earth 
ground to the grounding studs on each power supply. Use a hexagonal-head external 
drive socket wrench, with a minimum of 150 lb-in. (16 Nm) tightening torque, to 
connect the leads to the terminals.
Primary overcurrent protection is provided by the building 
circuit breaker. This breaker should protect against excess 
currents, short circuits, and earth faults in accordance with 
NEC ANSI/NFPA70.
If using a fixed-size nut driver or wrench to tighten and 
loosen the nuts, use only a 7/16-in. tool. Do not substitute 
a metric tool, because a tool that does not fit the nuts 
exactly can damage them. If a 7/16-in. tool is not available, 
use pliers or an adjustable wrench.