Confirming Unit Settings and Design Contents
FP2−CCU
3 − 5
3.2 Confirming the I/O Allocation and Root No.
3.2
Confirming the I/O Allocation and Root No.
3.2.1
I/O Allocation
A 16 points (16SE) I/O number is automatically allocated to the slot in which the Computer
Communication Unit is installed.
This can be changed to 0 point (0SE) if desired, using tool software.
SD RD ERR SD RD ERR AL
COM.2
COM.1(RS232C)
COM.2(RS232C)
CPU unit
Computer Communication Unit
X0
XF
(WX0)
Y10
Y1F
(WY1)
Y20
Y2F
(WY2)
Y40 to Y4F (WY4)
to
to
to
16
−point
input
unit
16
−point
output
unit
16
−point
output
unit
16
−point
output
unit
30 to 3F are occupied.
CCU
COM.1
Notes
If there are any empty slots between the CPU unit and the
Computer Communication Unit, check to see if an I/O area has
been allocated for the empty slot(s).
When I/O mount allocations are made, or automatic allocation
is carried out, 16 points are automatically allocated to each
empty slot.
If the CPU unit being used is a dual−module type, make sure
any occupied I/O areas incorporated in the CPU unit are also
checked.