Panasonic FP2 Benutzerhandbuch

Seite von 56
Specifications
FP2−CCU
6 − 3
6.1
Specifications
6.1
Specifications
General Specifications
Item
Specifications
Ambient temperature
0 to 55 °C/32 to 131 °F
Storage temperature
–20 to +70 °C/– 4 to + 158°F
Ambient humidity
30 to 85 % RH (at 25°C non−condensing)
Storage humidity
30 to 85 % RH (at 25°C non−condensing)
Vibration resistance
10 to 55 Hz, 1 cycle/min.: double amplitude 0.75 mm (0.03 in.),
10 min. on 3 axes
Shock resistance
Min. 98 m/s
2
, 4 times on 3 axes
Noise resistance
1000 V
p−p
, 50 ns, 1 μs pulse widths (based on in−house measurements)
Operating condition
Free of corrosive gases and excessive dust
Computer Communication Unit Performance Specifications
Item
Specifications
Interface
Two RS232C ports
Transmission distance
Max. 15 m/49.212 ft
*1
Transmission speed (Baud rate)
19,200/9,600/4,800 bits/s, selectable using DIP switch
Communication method
Half duplex
Synchronous method
Start−stop synchronous method
Transmission code
ASCII
Transmission data format
Stop bit: 1−bit
Parity: Valid (odd)
Character bits: 7−bit/8−bit, selectable using DIP switch
Data transmission order
0 bit first in units of characters
End terminal code
CR (0DH)
Computer linking Message
Header (%) to terminator (CR) Once transmission rights from the
host computer are received, com-
Maximum message length Max. 118 characters/frame
(including “%” and “CR”)
host computer are received, com
munication is started. The commu-
nication protocol is MEWTOCOL−
COM.
Current consumption
60 mA or less (at 5 V DC)
Weight
Approx. 120 g/4.233 oz
*1: The value is given as 15 m/49.212 ft. in the specifications, but if used in an environment with a high noise level,
communication may be unstable. Check the conditions using the actual device.
Note
This unit does not support extension header (<). Use the Multi
Communication Unit.