Toshiba 1000 Benutzerhandbuch

Seite von 64
 
 
 
16 
5.5 
Front Panel Settings 
Listed below are the default settings of the primary UPS parameters. 
 
Settings 
Options 
Default 
Remarks 
1) O/P VOLT SET 
 (output voltage       
set) 
100/110/115/120/127 
208/220/230/240 Vac 
120 V 
230 V 
 
120 V (FOR LV series) 
230 V (FOR HV series) 
2) I/P FREQ SET 
(input frequency 
setting) 
+/- 2% 
+/- 5% 
+/- 7% 
+/- 5% 
Input Frequency range in 
Free Run mode 
3) I/P BYPASS 
SET 
(input bypass  
setting) 
+/- 10% 
+10% -15% 
+15% -20% 
+10% 
-15% 
Input Voltage range when 
Bypass mode is on 
4) FREE RUN 
SET 
 
ON/OFF 
 
ON 
 
If ON, enable UPS runs on 
Asynchronous  mode. 
   For example: 
If input freq 55Hz  
output freq stays at 60Hz. 
 
If OFF, disable UPS runs on 
synchronous mode. 
For example: 
If input freq 55Hz,  
UPS will go to battery mode. 
5) HE MODE SET 
 
ON/OFF 
 
 OFF 
  
 
If ON, enable UPS runs in 
High efficiency  mode.  The 
unit will be in bypass mode 
with  95% or higher 
efficiency. 
 
If OFF, the unit will be in the 
online mode with 85% 
efficiency. 
6) MANUAL 
BYPASS 
ON/OFF 
OFF 
If ON, enable UPS switch to 
Bypass mode immediately.