1. Overview
By using RS-485 Option Unit, a network can be constructed that allows communication between a host
computer and multiple ASD units. A maximum of 32 Option Units can be connected on the same
network. And two ASDs can be connected to one Option Unit. A maximum of 64 ASDs can be connected
on the same network. (If ASD has a CPU whose version is V104 or V103, a maximum of 32 ASDs can
be connected on the same network.)
computer and multiple ASD units. A maximum of 32 Option Units can be connected on the same
network. And two ASDs can be connected to one Option Unit. A maximum of 64 ASDs can be connected
on the same network. (If ASD has a CPU whose version is V104 or V103, a maximum of 32 ASDs can
be connected on the same network.)
2. Communication specifications
Item
Specifications
Interface
Conforming to EIA RS485 standard
Configuration
4-wire, bus type (terminating resistor is necessary at
each end of system)
each end of system)
Communication Distance
1,000m maximum
Connection Points
32 units maximum
Number of ASDs per one Option Unit
2 units maximum
Number of ASDs on the Same Network
64 units maximum (If ASD has a CPU whose version
is V104 or V103, a maximum of 32 ASDs can be
connected on the same network.)
is V104 or V103, a maximum of 32 ASDs can be
connected on the same network.)
Communication Line Isolation
Not isolated
Synchronization Method
Start-stop synchronization
Error Detection Method
Parity, checksum
Communication Speed
1200/2400/4800/9600 baud selectable (parameter
and switch selection)
and switch selection)
Data Code
ASCII code, binary code
Other
Time-out function available