If the EOI is already connected via the RS485/RS232 channel, then no change is 
required. 
6.  Connect the drive’s common serial communication port (CNU2) to one of the 
channels (A, B or C) of the ETH-100 with the communication cable 
(communication cable is not included with the interface kit).  When choosing 
cables for this connection, standard 24 AWG category 5 (CAT5) unshielded 
twisted-pair (UTP) 8-conductor cables found in Ethernet networks in most office 
environments can be used.  The maximum allowable length for these cables is 5 
meters.  Although there are many varieties and styles of CAT5 UTP cables 
available, ICC strongly recommends using only high-quality cables from reputable 
manufacturers to guarantee optimal noise immunity and cable longevity.  Ensure 
that each end of the cable is fully seated into the modular connector, and route 
the cable such that it is located well away from any drive input power or motor 
wiring.  Also take care to route the cable away from any sharp edges or positions 
where it may be pinched. 
7.  Reinstall the drive’s front cover / close the drive’s cabinet door. 
8.  Repeat steps 1, 2, 4, 5, 6 and 7 to connect other drives as needed. 
9.  Connect the Ethernet network cable to the shielded RJ45 connector marked 
“Network” on the bottom of the unit.  If a ground cable is going to be used, attach 
the ground cable to the screw terminal marked “GND” on the bottom side of the 
unit (refer to section 4).  Ensure that the network cable is fully seated into the 
modular connector, and route the cable such that it is located well away from any 
drive input power or motor wiring.  Also take care to route the cable away from 
any sharp edges or positions where it may be pinched. 
10. Take a moment to verify that the ETH-100 and all network cables have sufficient 
clearance from drives, motors, or power-carrying electrical wiring. 
11. Turn the power sources to all connected drives ON, and verify that the drives 
function properly.  If the drives do not appear to power up, or do not function 
properly, immediately turn power OFF.  Repeat steps 1 and 2 to remove all 
power from the drives.
  Then, verify all connections.  Contact ICC or your local 
drive distributor or manufacturer for assistance if the problem persists. 
 
 
3.2  Installation for S7, S9 and A7 Drives 
1. 
 
CAUTION!
  Verify that all input power sources to the drives to be 
connected have been turned OFF and are locked and tagged out. 
2. 
 
DANGER!
 
 Wait at least 5 minutes for the drive’s electrolytic 
capacitors to discharge before proceeding to the next step.  Do not touch any 
internal parts with power applied to the drive, or for at least 5 minutes after 
power to the drive has been removed.  A hazard exists temporarily for 
electrical shock even if the source power has been removed.
  Verify that the 
CHARGE LED has gone out before continuing the installation process. 
3.  Attach the mounting clip and unit enclosure in your desired manner (refer to page 
11 for more information).