Siemens bacnet 125-5037 Benutzerhandbuch

Seite von 48
Point Database 
22 
 
Siemens Building Technologies, Inc. 
Descriptor Address
Application Description 
NGT OVRD 
{21}
All except 
2597 
Indicates the mode that the controller is operating in 
with respect to the override switch. NIGHT indicates 
that the switch has not been pressed and the 
override timer is not active. DAY indicates that the 
switch has been pressed and the override timer is 
active. The controller then uses a day mode 
temperature setpoint. This point is only in effect 
when DAY.NGT indicates night mode. 
REHEAT START 
22 
All except 
 2560, 2561,  2597 
 
Determines how the reheat modulation will be 
sequenced while in heating mode. When HTG 
LOOPOUT is above this value, then the reheat 
modulates upward. 
REHEAT END 
23 
All except 2560,  
2561, 2597 
 
Determines how the reheat modulation will be 
sequenced while in heating mode. When HTG 
LOOPOUT is below this value, then the reheat 
modulates downward. 
DI 2 
{24} 
All 
Actual status of a contact connected to the 
controller at DI 2. ON indicates that the contact is 
closed; OFF indicates that the contact is open. If a 
wall switch is used, it is connected to DI 2. See 
WALL SWITCH. 
DI 3 
{25}
All except 
2561 
Actual status of a contact connected to the 
controller at Al 3/DI 3. ON indicates that the contact 
is closed; OFF indicates that the contact is open. 
When a contact is connected at DI 3, Al 3 is not 
available. See AUX TEMP. 
SERIES ON 
26 
2564, 2565 
When flow rises above this value, the series fan will 
turn ON. 
SERIES ON 
26 
2566 
This point is present, but not used in this 
application. 
SERIES OFF 
27 
2564, 2565 
When flow drops below this value and other 
conditions have been met, the series fan will turn 
OFF. 
SERIES OFF 
27 
2566 
This point is present, but not used in this 
application. 
PARALLEL ON 
28 
2564 
This point is present, but not used in this 
application. 
PARALLEL ON 
28 
2566, 2567  
When flow drops below this value and other 
conditions have been met, the parallel fan will turn 
ON. 
DAY.NGT {29}  All 
Indicates 
the 
mode in which the controller is 
operating. Day temperature setpoints will be used in 
day mode. Night temperature setpoints will be used 
in night mode. This point is normally set by the field 
panel. 
PARALLEL OFF 
30 
2564 
This point is present, but not used in this 
application.