LST fc600-tdiff-57 Benutzerhandbuch

Seite von 1
0832–CPD–0127
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
FC600-TDIFF-57_DBL_LST_EN_0850.PDF • PAGE 1
A
Building Safety. Building Security.
•  Addressable conventional technology
•   Individual detector identifi cation with 
optional address module
•  Maximum temperature 57°C
•   Allows for the connection of an 
external remote indicator
•   Anti-tamper locking feature on 
detector base
•   Function check by means of test 
magnet
Description
Specifi cations
The  Thermal  Rate-of-Rise  Detector  FC600/TDIFF/57 
will  respond  to  temperatures  above  57°C  (EN 54 -5 
class A1R) or an abrupt rise in temperature. It can be 
used in rooms with a height of up to 7.5m. Any alarm 
will be transmitted to the fi re detection panel in con-
ventional technology. An individual detector identifi ca-
tion can be obtained with the optional Address Module 
NG58-1.
The detector is equipped with an LED indicator which 
is visible from all sides at any angle and thus facilitates 
easy identifi cation of the alarming detector. In addition, 
a remote indicator can also be connected.
Several types of detector bases are available to faci-
litate quick and easy installation. To prevent unautho-
rized removal of the detector, all detector bases are 
equipped  with  an  anti-tamper  locking  feature.  A  de-
tector function test can be conveniently conducted by 
using a test magnet.
Operating voltage 
10 – 30VDC (supply through detector line voltage)
Current consumption 
typ. 40µA (normal condition)
Alarm temperature 
57°C (maximum-heat component)
Operating temperature 
max. +45°C
Ambient temperature 
-30°C to +70°C
Relative humidity 
max. 95% (no condensation)
Dimensions ø × h (without base) 
106 × 46 (mm)
Colour 
white
Weight 
80g
Approvals 
LPCB 603b/02
 
0832-CPD-0127
Order number 
242070
Order name 
Thermal ROR Detector/Conv./FC600 FC600/TDIFF/57