Cyclops Frame Store CCTV Module V1.0 - Page 1 of 1
CORTECH DEVELOPMENTS LTD
CYCLOPS Frame Store
CCTV Module V1.0
Overview
Datalog software module for operation with the VRC Cyclops freeze frame unit, to control the recording of
alarm frames by the Cyclops.
Connections
Operation
The Datalog software will upon alarm provide control signals to a suitable output relay provided by the
installer. This output should be connected by the installer to the alarm input for camera one. On the
first alarm this output will trigger the frame store. Because of the speed limitations of clearing the
Cyclops frame store before further alarm triggering, only the first alarm will trigger storage.
When an alarm is ‘Accepted’ by an operator, then the Datalog will select camera 1 channel. Once any
alarm is reset by the operator, the Datalog will issue the following key press actions automatically via
an RS232 port.
1. Clear
2. Clear
Since the keyboard port only supports one keyboard, the Cyclops keyboard must be disabled in order
for correct operation.
The Cyclops unit should be programmed as follows:
  Camera 1: Capture all frames after trigger
  Alarm sequence: Autoplay Mode
Rx
Gnd
Tx
Ov
Datalog
Computer
VRC Cyclops
Notes: Cyclops on Datalog port COM4, Alarm = C-Lem 49
Com
Port
8
7
6
Alarm
Cam 1
Relay
Downloaded from:
 http://www.guardianalarms.net