GE EPM 5200 Benutzerhandbuch

Seite von 100
 
CHAPTER 3: ELECTRICAL INSTALLATION 
GE Industrial Systems                               5300P  Advanced Power Meter
 
CHAPTER 3 
ELECTRICAL INSTALLATION 
 
 
3.1: Connecting the Current Circuit 
 
Install the wiring for the current at 600V AC insulation as a minimum. The cable connector should be 
rated for 6 Amps or greater and have a cross-sectional area of 16 AWG minimum. 
 
Mount the current transformers (CTs) as close as possible to the meter for best accuracy. The following 
table illustrates the maximum recommended distances for various CT sizes, assuming the connection is 
via 16 AWG cable. 
 
CT Size 
Maximum Distance  (CT to Meter) 
2.5 VA 
10 F
EET
 
5.0 VA 
15 F
EET
 
7.5 VA 
30 F
EET
 
10.0 VA 
40 F
EET
 
15.0 VA 
60 F
EET
 
30.0 VA 
120 F
EET
 
Table 3.1: CT Size and Maximum Distance 
 
WARNING
DO NOT leave secondary of the CT open when primary current is flowing. This causes high voltage that 
will overheat the secondary of the CT. Use a shorting block on the secondary of the CT. 
 
 
3.2: CT Connection  
 
If the meter is connected directly to the current (up to 10 Amps max.), maintain the exact connection to 
avoid incorrect polarity.  
 
When the meter is connected using the CTs, you must maintain the correct CT polarities. CT polarities 
are dependent upon correct connections of CT leads, and upon the direction the CTs are facing when 
clamped around conductors. The dot on the CT must face the line side; the corresponding secondary 
connection must connect to the appropriate input on the meter.  Failure to connect CTs properly results in 
inaccurate power readings. If your meter is not reading power properly, it is more than likely the CT is 
incorrectly wired. 
 
NoteCTs are shorted if connected to the terminal block model DSP2 or 3 even if it is detached 
from the meter. 
 
HELPFUL DEBUGGING TOOLS 
 
O
PTION 
1: I
SOLATING A 
CT C
ONNECTION 
R
EVERSAL POWER READING 
 
 
If your meter does not read the correct watts after installation, it almost always means that the CT’s have 
been wired in the wrong polarity. To check the polarity of the CT after the monitor has been installed, look 
at the single phase WATT readings to see that each of the readings are positive (assuming you are 
consuming power). If one of the WATT readings is negative, that particular phase CT is reversed. 
To check the single phase WATT reading, press the Power button twice while the annunciator is 
positioned to WATTS. Then press the Phase/Next button to cycle through the phases. After connecting 
the polarity of the CTs, the WATT and VAR readings should be correct.