CHAPTER 6: PROGRAMMING OVERVIEW 
38 
EPM 5000 series Advanced Power Meters                                GE Multilin
 
 
6.3: Programming Mode Data Entry 
 
The EPM 5300P and EPM 5200P programming mode utilizes only three out of the five-keypad buttons: 
the MAX/MIN/LIMITSVOLTS/THD, and AMPS/THD buttons. 
 
THD
THD
MAX/MIN
LIMITS
VOLTS
  
AMPS
POWER
PHASE
  NEXT
U
SED FOR 
P
ROGRAMMING
U
SED FOR
P
ASSWORD 
E
NTRY
 
 
Note: The EPM 5200P uses the same keypad strokes and methods. Although the keypad may look 
slightly different, the keys match the EPM 5300P exactly. In the interest of brevity, all keystrokes and 
programming functions are shown using the EPM 5300P keyboard.  
 
 
BUTTON FUNCTION 
DESCRIPTION 
MAX/MIN/LIMITS  ADVANCES 
Scrolls GROUPS, FUNCTIONS and advances to exit point from 
FUNCTION and GROUP level. 
VOLTS/THD CHANGES 
VALUE 
Scrolls PACKS, digit counters and changes switch PACK position UP or 
DOWN. 
AMPS/THD 
STORES 
Activates new data entry and enters or exits from GROUP or FUNCTION 
level. 
 
 
6.4: Standard Numeric Data Entry 
 
Programmable FUNCTION values are always four digit numerical fields designed to accept any value 
between 0000 and 9999 (a blank signifies a zero).  When entering the value of a FUNCTION, enter all 
four digits, leading zeros included.  For instance, to enter the number 25, enter 0025.