CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP 
GE Multilin                                           EPM 5000 series Advanced Power Meters
 
55 
9.9: Group 0, Function 6—KYZ Parameter Selection 
 
NOTE: FUNCTION 6 applies only if Option -NL or -NL2 was ordered. 
 
OPTION -NL: This option gives the meter 2 Relays and one KYZ pulse.  The KYZ pulse can be 
programmed to the below features. 
 
Select a single parameter from Table 9-5 according to the EPM 5300P model being programmed. 
 
 
 
OPTION -NL2: This option offers 3 distinct KYZ pulses instead of Relays.  
Only three separate parameters may be selected:  FUNCTION 6.0 (KYZ Port 0), FUNCTION 6.1 (KYZ 
Port 1), and FUNCTION 6.2 (KYZ Port 2). The available parameters vary according to the EPM 5300P 
model being programmed. For exact port positions see Installation Sections. 
 
 
 
 
PARAMETER DESCRIPTION 
0 Disable 
KYZ 
Positive Watt Hour KYZ 
VA Hour KYZ 
Negative Watt Hour KYZ 
Positive VAR Hour KYZ 
Negative VAR Hour KYZ 
Table 9-5: KYZ Parameters 
 
 
 
APPLICABLE SELECTIONS:  5300P - +WH, -WH, VAH 
 
 
 
           5300P+R* - +WH, -WH, +VARH, -VARH 
 
 
        * (-R option gives the 5300P VAR/Hour readings instead or VA/Hours). 
 
To perform the KYZ Parameter Selection: 
 
NOTE:  Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch. 
 
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
 
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
 
Step 1: 
a. Enter Group Level of Programming Mode  
    (see Chp. 8).  
 
b. Press MAX/MIN/LIMITS until 0. appears in 
     upper display.  
 
c. Press AMPS to activate the Group.  
 
Step 2: 
a. Press MAX/MIN/LIMITS until 06.P appears in  
    upper display. 
 
  (Standard Selection is 1).