CHAPTER 15: PROGRAMMING QUICK REFERENCE 
GE Industrial Systems                               5300P  Advanced Power Meter
 
85 
CHAPTER 15 
PROGRAMMING QUICK REFERENCE 
 
 
 
 
15.1: Entering the Programming Mode 
 
1. Hold 
PHASE/NEXT key and press AMPS key. 
2.  Display blanks and shows either a ‘0’, 
‘1’, or ‘3’. 
3.  If ‘3’ is not displayed then press AMPS key until ‘3’ is displayed. 
4. Release 
AMPS key and press PHASE/NEXT key, while ‘3’ is still displayed.  
5.  Display shows ‘333’ momentarily. 
6.  Upper display starts counting. Press PHASE/NEXT key when ‘5’ is displayed to register the ‘5’. 
7.  Repeat step 6 until ‘555’ has been registered. 
 
15.2: Data Entry Sequence 
 
1.  At programmable numerical fields or Switch Pack fields, Press AMPS key to begin Data Entry 
Sequence. 
2.  The current setting moves to middle row of display and dashes appear in the bottom row. Press 
VOLTS key to toggle between available choices. 
3.  When a correct choice is selected, press AMPS key to store. 
 
15.3: Programming Groups 
 
Programming 
groups 
Description 
Global Meter Setup—Integration Interval, Meter Address, 
Communication Setting, Relay Settings 
Full Scale Settings. Voltage Full Scale, Current Full Scale and Power 
Function Full Scale. 
Meter Calibration 
Calibration Ratios 
Volts and Current Limits 
Power Function Limits 
THD Limits 
Imbalance Reversal Limits 
DC Output Calibration