GE EPM 5200 Benutzerhandbuch

Seite von 100
CHAPTER 16: ETHERNET OPTION 
92 
EPM 5000 series Advanced Power Meters                                GE Multilin
 
 
 
 
See the Table below for a description of the Status LED functions. 
 
LED Description 
LED 
Functions 
1 Serial 
Port 
(Channel) 1 
Status 
Lights solid green to indicate Channel 1 is IDLE. 
Blinks green to indicate Channel 1 is connected 
to the network and ACTIVE. 
2 Serial 
Port 
(Channel) 2 
Status 
 
Lights solid yellow to indicate Channel 2 is IDLE. 
Blinks yellow to indicate Channel 2 is connected 
to the network and ACTIVE. 
(Not used by this device; reserved for future use) 
Diagnostics 
Blinks or lights solid red in combination with the 
green (Channel 1) LED to indicate 
DIAGNOSTICS and ERROR DETECTION. 
 
Red solid, green (Channel 1) blinking: 
   1x: EPROM checksum error 
   2x: RAM error 
   3x: Network controller error 
   4x: EEPROM checksum error 
   5x: Duplicated IP address on network* 
   6x: Software does not match hardware* 
 
Red blinking, green (Channel 1) blinking: 
   4x: Faulty network connection* 
   5x: No DCHP response received* 
 
4 Network 
Link 
Status 
Lights solid green to indicate network port is 
connected to the network. 
 
 
* non-fatal error 
 
 
16.2: Ethernet Option Setup 
 
This chapter covers the required steps to get the Ethernet Interface on-line and working.  There is only 
one method used to log into the Ethernet Server and set up the IP address:   
 
•  Network Port Login: make a Telnet connection to the network port (9999). 
 
It is important to consider the following points before logging into and configuring the Ethernet Interface: 
 
•  The Ethernet Interface’s IP address must be configured before a network connection is available. 
 
•  Only one person at a time may be logged into the network port.  This eliminates the possibility of 
several people trying to configure the Ethernet Interface simultaneously.