Omron ethernet direct dr 170 14 Benutzerhandbuch

Seite von 70
Klinkmann Automation Omron Ethernet DAServer 
35 
 
 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4                                                                 17014m14  
CHAPTER 4 
Item Names 
The Omron Ethernet DAServer supports item/point names consistent with the point 
naming conventions used by OMRON PLCs and programming software.  The Server 
supports almost all memory areas of the following OMRON PLC types: CS1, CJ1, 
C200HX, C200HG, C200HE, CV-series, C-series, CPM2x and CQM1. 
 
Contents 
• 
Item Name General Format 
• OMRON PLC’s Item Naming 
• DAServer Standard System Items 
• Generic OPC Syntax 
 
Item Name General Format 
In this section the general Item naming conventions used by OMRON Ethernet DAServer 
are explained. 
  
Each Integer, Discrete or Floating Point item generally may be described as: 
 
PnS 
 
Each item, representing bit in word, may be described as: 
 
Pn:b (or Pn:bb or Pn.b or Pn.bb
 
Each ASCII string item generally may be described as: 
 
Pn-PhS 
 
where: 
 
n - 
specifies the Memory area word/bit address of the specific word, flag or bit or 
lowest-numbered address of ASCII string. 
 
(bb) - specifies the bit number in word (b can be 0…9 and bb can be 00…15). Number 
of digits in bit item name with separator is not relevant (leading zeroes are not 
necessary).  
 
- 
Specifies the highest -numbered address of ASCII string.  
 
P - 
optionally used prefix, one, two or three characters before Memory area address, 
and designates the type of Memory area. 
 
S
 - 
optionally used suffix - a letter after address, which is used to change the default 
format of data. The following presents the OMRON Ethernet DAServer supported 
data formats and suffixes, indicating corresponding format. 
 
Unsigned/Signed Format 
The server interprets 16-bit word in a PLC in 16-bit unsigned format (value limits 0 
to 65535) or signed format (value limits -32768 to 32767). Unsigned quantities may 
be read by one of two methods - by entering item name without suffix or appending 
the suffix 'U' (or 'u') to the item name. For example, channel DM100 in a PLC