Unattended Start Protection
If the Run command is already set when power is turned ON, the inverter starts running 
immediately after powerup. The Unattended Start Protection (USP) function prevents 
that automatic startup, so that the inverter will not run without outside intervention. 
When USP is active and you need to reset an alarm and resume running, either turn the 
Run command OFF, or perform a reset operation by the terminal [RS] input or the 
keypad Stop/reset key.
In the figure below, the [UPS] feature is enabled. When the inverter power turns ON, the 
motor does not start, even though the Run command is already active. Instead, it enters 
the USP trip state, and displays E13 error code. This requires outside intervention to 
reset the alarm by turning OFF the Run command per this example (or applying a reset). 
Then the Run command can turn ON again and start the inverter output.
Inverter output frequency
Inverter power supply
[USP] terminal
Alarm output terminal
RUN command [FW, RV]
Run
command
Alarm
cleared
Alarm
display
E13
t
1
0
1
0
1
0
1
0
1
0
Events:
Option
Code
Terminal 
Symbol
Function Name
Input 
State
Description
13
USP
Unattended Start 
Protection
ON
On powerup, the inverter will not resume a Run 
command (mostly used in the US)
OFF
On powerup, the inverter will resume a Run 
command that was active before power loss
Valid for inputs:
C_01, C_02, C_03, C_04, 
C_05
Required settings:
(none)
Notes:
Note that when a USP error occurs and it is 
canceled by a reset from a [RS] terminal input, the 
inverter restarts running immediately.
Even when the trip state is canceled by turning the 
terminal [RS] ON and OFF after an under voltage 
protection E09 occurs, the USP function will be 
performed.
When the running command is active immediately 
after the power is turned ON, a USP error will 
occur. When this function is used, wait for at least 
three (3) seconds after the powerup to generate a 
Run command.
Example (default input configuration shown 
for –FU models; –FE and –FR models 
require input configuration—
see page 
):
See I/O specs on page 
1
2
3
4
5
L
P24
USP