Dynamic Braking
Introduction
The purpose of dynamic braking is to improve the ability of the inverter to stop (deceler-
ate) the motor and load. This becomes necessary when an application has some or all of 
the following characteristics:
• High load inertia compared to the available motor torque
• The application requires frequent or sudden changes in speed
• System losses are not great enough to slow the motor as needed
When the inverter reduces its output frequency to decelerate the load, the motor can 
temporarily become a generator. This occurs when the motor rotation frequency is 
higher than the inverter output frequency. This condition can cause the inverter DC bus 
voltage to rise, resulting in an over-voltage trip. In many applications, the over-voltage 
condition serves as a warning signal that we have exceeded the deceleration capabilities 
of the system. The L100 inverter can connect to an external braking unit, which sends 
the regenerative energy from the motor during deceleration to the optional braking resis-
tor(s). The dynamic braking resistor serves as a load, developing heat to stop the motor 
just as brakes on an automobile develop heat during braking.
A switching circuit and power resistor are the main components of the dynamic braking 
unit that includes a fuse and thermally activated alarm relay for safety. However, be 
careful to avoid overheating its resistor. The fuse and thermal relay are safeguards for 
extreme conditions, but the inverter can maintain braking usage in a safe zone.
Dynamic Braking Usage
Dynamic braking usage must follow guide-
lines to avoid overheating. The timing diagram 
to the right shows the output frequency versus 
time. Dynamic braking is in effect during the 
deceleration ramp, and has the following 
constraints: 
• Dynamic braking maximum duty cycle
= 10%, where T
b
/T
c
 
≤ 0.1 sec.
• Dynamic braking maximum continuous ON 
time T
b
 
≤ 10 sec.
Selecting Braking Resistors for External Braking Units
200V Class Inverters – The following tables 
specify the braking options for 200V class 
L100 inverters and the braking torque for each 
option. You can connect a single braking unit 
to the inverter, or two braking units for 
additional stopping torque.
Output
freq.
T
b
t
T
c
Dynamic braking
Inverter
+
Braking
unit
Braking
unit