Hitachi L100 Benutzerhandbuch

Seite von 192
Restoring Factory Default Settings
T
roub
leshooting
and Maintenance
6–8
Restoring Factory Default Settings
You can restore all inverter parameters to the original factory (default) settings for the 
intended country of use. After initializing the inverter, use the powerup test in Chapter 2 
to get the motor running again. To initialize the inverter, follow the steps below.
NOTE: Initialization cannot be performed with a remote operator panel. Disconnect the 
device and use the inverter’s front panel keypad.
No.
Action
Display
Func./Parameter
1
Use the 
, and 
 keys to 
navigate to the “B” Group.
“B” Group selected
2
Press the 
 key.
First “B” parameter selected
3
Press and hold the 
 key until ->
Country code for initialization 
selected
4
Press the 
 key.
00 = Japan, 01 = Europe,
02 = U.S.
5
Confirm the country code is correct. Do not change it unless you are absolutely sure the 
power input voltage range and frequency match the country code setting.
To change the country code, press
  
or  
to set, 
 to store.
6
Press the 
 key.
Country code for initialization 
selected
7
Press the 
 key.
Initialization function selected
8
Press the 
 key.
00 = initialization disabled, 
clear fault history only
9
Press the 
 key.
01 = initialization enabled
10
Press the 
 key.
Initialization now enabled to 
restore all defaults
11
Press and hold the 
, and
 
 keys. Do not release yet.
First part of special key 
sequence
12
Holding the keys above, press and 
hold the 
 
(STOP) key for 3 sec.
Final part of special key 
sequence
13
Release only the 
 (STOP)
 key, 
and wait for the display 
d
  0 1
 to 
appear and begin blinking.
Initialization begins when 
display starts blinking
14
Now release the 
, , 
and  
keys only after the 
d
  0 1
 display 
function begins blinking.
 
 
Default parameter country code 
shown during initialization 
process (left-most char displays 
alternating pattern) 
15
Initialization is complete.
Function code for output 
frequency monitor shown
FUNC.
1
2
b
  - -
FUNC.
b
  0 1
1
b
  8 5
FUNC.
  0 2
1
2
STR
FUNC.
b
  8 5
2
b
  8 4
FUNC.
  0 0
1
  0 1
STR
b
  8 4
FUNC.
1
2
b
  8 4
STOP
RESET
b
  8 4
STOP
RESET
d
  0 1
FUNC.
1
2
  E U
  U S A
d
  0 1