Honeywell ml6874 Benutzerhandbuch

Seite von 6
ML6874  
WIRING  
SPDT  
Controller 
ML6874 
28 Vdc 
OR 
+
T6 
T5 
24 Vac 
L1 
L2 
T5 
T6
B
Caution: 
In multiple actuators connection, power supply to all 
actuators must be connected in a TRUE parallel fashion 
to reduce excessive voltage drop. DO NOT "daisy chain" 
i.e. connected to one actutator then branched to another. 
ML6874
T5 
T6
Allow 0.5 amps maximum for each device.  Actuators and controller can share same transformer providing the 
VA rating of the transformer is not exceeded and proper phasing is observed. 
Use configuration DIP switches to select device functions: Direct acting function (actuator stem moves upwards 
with R & B closed ) or Reverse acting function ( actuator stem moves downwards with R & B closed ). DO NOT 
reverse wiring. 
SPDT controller can be a low voltage Series 20 "on-off " or Series 60 "floating" (center-off) type. 
Configuration
 FUNCTION
DIP switches 
located adjacent
Direct Acting Mode
to the  input
terminal block 
Reverse Acting Mode
NOTE:  
Turn power off before setting the DIP switches.  
DIP SWITCH CONFIGURATION  
on 
off
1
2
3
on 
off
1
2
3
Fig. 7  Wiring  for  SPDT controller to ML6874 actuators  