Outback Power Systems vfx 3524m Benutzerhandbuch

Seite von 65
Installation & Programming Manual
                               
FX & VFX Series Inverter/Charger System                   
Copyright 2003  
  OutBack Power Systems, Inc. 
 
 
   
900-0027-1 
                                                             19009 62
nd
 Ave NE, Arlington   WA 98223 USA                     
Page 12                                         
Rev 7.2
       08/26/05                                                                    Tel 360 435 6030     Fax 360 435 6019  
INDICATORS & CONTROL WIRING  
The AC wiring compartment also encloses the following items; a 6-port terminal block, an RJ-11 jack, an RJ-45 jack, a set of three 
“Battery” LEDs and a set of three “Status” LEDs. The 6-port terminal block contains ports for Inverter & On/Off, AUX + & AUX –, and 
XCT + & XCT -.  The RJ-11 “Battery Temp” jack accepts only OutBack’s “RTS” battery temperature sensor.  Non-OutBack sensors may 
fit, but if their thermister value is not identical to the RTS’s, your battery bank could be destroyed.  The RJ-45 “MATE/HUB” jack accepts 
the CAT-5 cable that is included with the MATE and the HUB.  The “Battery” LEDs give a quick indication of the battery voltage.  The 
“Status” LEDs give a quick indication of whether the FX is inverting, has AC input power, or if an Error has occurred.   
The “Battery” LEDs operate at the following voltage levels: 
 
               
 
 
Nominal Battery Voltage 
LED 
Color 
  12 
VDC 
 
 24 
VDC 
 48 
VDC 
Green     
  
 
12.5 or higher       25.0 or higher 
50.0 or higher 
Yellow     
 
 
11.5 to 12.5 
23.0 to 25.0  
46.0 to 50.0 
Red  
 
 
 
11.5 or lower 
23.0 or lower 
46.0 or lower 
The “Status” LEDs operate under the following conditions: 
LED Color LED 
Action  
LED 
Indicates 
Green 
 Solid 
GREEN 
 Inverter 
ON 
 
 
Flashing GREEN  
Search Mode or Slave Power Save Mode 
  Off 
  Inverter 
OFF 
Yellow    
Solid YELLOW   
AC Source is connected 
 
 
Flashing YELLOW 
AC Input Live – Waiting to connect to the FX 
  Off 
  No 
AC 
Input 
Present 
Red 
 
Solid RED 
 
Error – An Error Message will be automatically displayed on the MATE 
 
 
Flashing RED 
 
Warning – A non-critical fault happened to the FX.  The MATE can access this info. 
INVERTER ON/OFF 
The left two terminals of the 6-port terminal block marked INVERTER and ON/OFF can be used to control the inverter’s output. 
Connecting the two terminals through a switch will allow control of the inverter output if a MATE is not available.  A small jumper wire is 
pre-installed into these two ports of the terminal block and must be removed in order to add the external switch.  If the FX’s AC output is 
off, check that the jumper wire is present and well connected.  An installed switch overrides the control provided by the OutBack MATE.  
If the switch is set to OFF, the MATE will not be able to turn ON the inverter.  The switch cannot put the FX into Search mode. 
AUXILIARY OUTPUT (AUX + / AUX -) 
The Auxiliary output system uses the AUX + and AUX – terminals and is able to be programmed through the MATE to do a variety of 
tasks. The default use for these terminals is to drive one 12-volt fan for external cooling. The power available at these terminals is 12 
VDC at 1.0 amps (12 watts) maximum.  These terminals should not be connected to any type of DC load which has a high inrush 
current requirement.  The FX includes internal electronic overcurrent protection for this 12 VDC output circuit which auto resets if it is 
short circuited.  No additional fuses are required.  Use the OutBack FX Turbo Kit or DC12-FAN for cooling.  For automatic or advanced 
generator start functions, the Auxiliary Output can drive a 12V automotive relay for the 2-wire starting circuitry of a generator.  OutBack 
Power Systems does not support 3-wire start generators; however, a 3-wire to 2-wire conversion kit is available from other sources. 
XCT + / XCT -       
These terminals are not operational at this time.
  
 
BATTERY TEMP {REMOTE TEMPERATURE SENSOR (RTS)}   
The OutBack FX has a 4 conductor “phone” RJ-11 modular jack located in the AC compartment for the connection of an optional 
external battery temperature sensor, the RTS (sold separately), that allows for automatic adjustment of the battery charging process 
based on the temperature of the battery.  Battery manufacturers provide recommended charge voltages based on temperatures of 25˚C 
/ 77˚F.  With the RTS attached, the FX adjusts the battery voltage 0.03 volts per degree Celsius for every 12-volts of battery present.  
When a HUB is used, the RTS must be plugged into the Master FX which must be plugged into port 1 of the HUB.  If this is the case, 
only one RTS is required for all devices plugged into the HUB.  The RTS should be stuck to the side of a battery below the electrolyte 
level so it can measure the temperature of the batteries.  The wire from the RTS can be folded and routed underneath the transparent 
gray plastic lexan cover of the AC wiring compartment to allow connection to the battery. There is a small indentation in the aluminum 
casting between the battery terminals to allow for the wire to pass without affecting the sealing of the covers.  When running additional 
wires under the smoked lexan cover, it may be required to snip some lexan away to allow for wire routing. The lexan will not crack 
when cutting or filing.  IMPORTANT:  Do not connect a different brand of battery temp sensor.  It may cause battery failure!!! 
MATE / HUB  
The 8 conductor “Ethernet” RJ-45 modular jack allows direct connection of a MATE system controller and display to the FX using 
standard CAT-5 type cabling.  If multiple FX’s or a FX and a MX charge controller are both in the system, an OutBack HUB 
communication manager is connected to this RJ-45 jack for stacking of the FX’s and for efficient system performance.  The HUB acts 
similarly to a computer hub to combine the communication signals of the devices together into a networked system.  OutBack offers two 
different HUB products at this time. The HUB-4 accepts up to four OutBack products and one MATE. The HUB-10 connects up to ten 
OutBack products and one MATE.  NOTE: Although the HUB has 2 ports for MATEs, only the 1
st
 port is operational.