STACKING INSTRUCTIONS 
System Examples (Continued) 
By making this FX the 1
st
 rank slave, we are turning both Legs “On” directly, thus producing 240VAC without using the X-240.   
If you have a system that is different from this example then press the PORT button until you get to a slave FX that is in series (“OB 
Slave L2”) with the master.  
On this screen the setting from the factory should be set to 1 which indicates the 1
st
 rank slave.  If it’s anything other than 1 then press 
the DEC button until it becomes 1.  Press the PORT button until you reach P02 to talk to the port 2 FX.   
If you have a system that is different from this example then press the PORT button until you get to a slave FX that is in parallel (“OB 
Slave L1”) with the master.   
Press the INC button to change the “POWER SAVE LEVEL SLAVE ADJUST ONLY” to 2 which is the 2
nd
 rank slave.  Press the PORT 
button twice to talk to the port 4 FX.   
If you have a system that is different from this example then press the PORT button until you get to the next slave FX that is in series 
(“OB Slave L2”) with the master.   
Press the INC button until the setting is 3 for 3
rd
 rank slave.   
Any additional FX’s in the system can be programmed by pressing the PORT button to get to the next FX and then press INC until the 
setting is 4 for the 4
th
 rank slave.  Continue this process, making sure each FX has its own “Slave Rank”, until you have set all FX’s. 
Let’s back track a little by going to the “POWER SAVE LEVEL MASTER ADJUST ONLY” menu.  Do this by pressing the DOWN 
button, TOP button, then DOWN button.  Verify that the screen you are on now is the “POWER SAVE LEVEL MASTER ADJUST 
ONLY” screen and change the port to P01.  Turn on all of your FX’s AC Output breakers.  The master FX’s “Inverter” LED should be 
solid and all the slaves “Inverter” LED’s should be blinking.  Adjust the “POWER SAVE LEVEL MASTER ADJUST ONLY” from 0 to 1 
and watch the 1
st
 slave’s (port 3) “Inverter” LED go solid.  When the “Inverter” LED is on solid, this means that the inverter is on.  When 
the “Inverter” LED on the slave is blinking, this means the FX is asleep.  Adjust the “POWER SAVE LEVEL MASTER ADJUST ONLY” 
to 2 and watch the 2
nd
 slave’s (port 2) “Inverter” LED turn on.  Adjust the “POWER SAVE LEVEL MASTER ADJUST ONLY” to 3 and 
watch the 3
rd
 slave’s (port 4) “Inverter” LED turn on.  If you have more than three slaves then keep increasing the value in the “POWER 
SAVE LEVEL MASTER ADJUST ONLY” screen and verify that each slave’s “Inverter” LED comes on as expected.  You have now 
verified that all FX’s are stacked correctly so adjust the “POWER SAVE LEVEL MASTER ADJUST ONLY” back down to 0 and have 
fun with your system!   
3-PHASE STACKED SYSTEM (3 FX’S ONLY) 
This type of system will include only three FX’s and must be set up as described here.  Turn off all AC Output and AC Input breakers 
before powering up FX’s.  In 3-phase stacking, I am assuming that the top FX is plugged into port 1 of the HUB, the 2
nd
 FX down is 
plugged into port 2 and the 3
rd
 FX down is plugged into port 3 (This is not a rule, just for simplicity).  The HUB has a jumper on it that 
needs to be changed for 3-phase stacking (refer to the HUB manual).  Using the MATE, go to the stacking menu (explained earlier in 
the “Stacking Instructions” section).  You are now at the 1
st
 stacking menu called “Stack Phase”.  In the upper right hand corner of the 
mate screen will always be the HUB port number of the FX you’re working with at the time.  Let’s start out with the FX that’s on port 1.  
If something other than P01 appears in the upper right hand corner then press the PORT button until P01 appears.  Set the “Stack 
Phase” of the port 1 FX to “3ph Master”.  The Master FX is considered phase A.  Press the PORT button and verify that the label in the 
upper right hand corner displays P02.  We are still in the “Stack Phase” menu but we are now talking to the FX on port 2.  Push the INC 
button five times to set the “Stack Phase” to “3ph Slave”.  Now you’ve set this FX (P02) as phase B, producing 208VAC between itself 
and the master (P01).  Press the PORT button again and verify that the label in the upper right hand corner displays P03.  We are still 
in the “Stack Phase” menu but we are now talking to the FX on port 3.  Push the INC button five times to set the “Stack Phase” to “3ph 
Slave”.  Now you’ve set this FX (P03) as phase C, producing 208VAC between itself and the master (P01) and also 208VAC between 
itself and the FX on phase B.  The next two screens in the STACK menu do not apply to a 3-phase system, so you need not worry 
about them.  Remember that the AC input to a 3-phase system must be a 3-phase source (generator or grid).  Have fun with your 
system!